1-8
General Information
BE1-951
OPERATIONAL SPECIFICATIONS
BE1-951 relays have the following features and capabilities.
Metered Current Values And Accuracy
Current Range:
5A: 0.5 to 15
1A: 0.1 to 3.0
Accuracy:
±1% of reading, ±1 least significant digit at 25
C
Temperature Dependence:
±0.02% per
C
Metered Voltage Values And Accuracy
Voltage Range
3 wire:
0 to 300 V
L-L
4 wire:
0 to 300 V
L-L
Accuracy (10 to 75 hertz)
50 V to 300 V:
±0.5% of reading, ±1 least significant digit at 25
C
Temperature Dependence:
±0.02% per
C
Metered Frequency Values And Accuracy
Frequency Range:
10 to 75 hertz
Accuracy:
±0.01 hertz, ±1 least significant digit at 25
C
Sensing Input
3-wire:
Phase A – B
4-wire:
Phase A – Neutral
Minimum Frequency Tracking Voltage:
10 V RMS
Calculated Values And Accuracy
Demand
Range:
0.1 to 1.5 nominal
Type:
Exponential
Accuracy:
±1% of reading ± 1 digit at 25
C
Temperature Dependence:
±0.02% per
C
Interval:
1 to 60 minutes
True Power
Range:
5 Ampere CT:
-7,500 kW to +7,500 kW
1 Ampere CT:
-1,500 kW to + 1,500 kW
Accuracy:
±1% at unity power factor
Reactive Power
Range:
5 Ampere CT:
-7,500 kvar to +7,500 kvar
1 Ampere CT:
-1,500 kvar to +1,500 kvar
Accuracy:
±1% at zero power factor
Energy Data Reporting
Range:
5 Ampere Unit:
100MWh
1 Ampere Unit:
100MWh
Units of Measure:
Kilo, Mega, Giga
Rollover value of Registers:
100,000
Accuracy:
±1% at unity power factor
Содержание BE1-951
Страница 157: ...BESTlogic Programmable Logic BE1 951 7 2 Figure 7 1 BESTlogic Function Blocks Courtesy of NationalSwitchgear com...
Страница 238: ...BE1 951 Human Machine Interface 10 5 Figure 10 5 Metering Menu Branch Structure Courtesy of NationalSwitchgear com...
Страница 239: ...10 6 Human Machine Interface BE1 951 Figure 10 6 Reports Menu Branch Structure Courtesy of NationalSwitchgear com...
Страница 270: ...12 2 Installation BE1 951 Figure 12 1 BE1 951 S1 Case Dimensions Courtesy of NationalSwitchgear com...
Страница 274: ...12 6 Installation BE1 951 Figure 12 5 BE1 951 H1 Case Dimensions Courtesy of NationalSwitchgear com...
Страница 283: ...BE1 951 Installation 12 15 Figure 12 16 Typical AC Connections Courtesy of NationalSwitchgear com...
Страница 394: ...A 18 Appendix BE1 951 Figure A 14 Time Characteristic Curve B Very Inverse 99 1376 Courtesy of NationalSwitchgear com...
Страница 396: ...A 20 Appendix BE1 951 Figure A 16 Time Characteristic Curve G Long Inverse 99 1622 Courtesy of NationalSwitchgear com...
Страница 397: ...BE1 951 Appendix A 21 Figure A 17 46 Time Characteristic Curve Courtesy of NationalSwitchgear com...