BE1-951 ASCII
Command
Interface
11-7
S2-67N=QVI
S2-24=0.0,0.0,0.0
S2-25=0.0,10.0,0.01,0
S2-25VM=20.0,80.0, 50m,DIS,DIS
S2-27P=0.00, 50m; S2-27X=0.00, 50m
S2-47=0.00, 50m
S2-59P=0.00, 50m; S2-59X=0.00, 50m
S2-81=00.00, 0m,O
S2-181=00.00, 0m,O
S2-281=00.00, 0m,O
S2-381=00.00, 0m,O
S2-481=00.00, 0m,O
S2-581=00.00, 0m,O
S2-81INH=40.0
S2-62= 0m, 0m
S2-162= 0m, 0m
S2-791= 0m; S2-792= 0m; S2-793= 0m; S2-794= 0m
S2-79R= 10s; S2-79F=1.0s; S2-79M= 60s
S2-79SCB=0
SP-60FL=ENA,PNQ
SP-79ZONE=0
SP-BF= 0m
SP-CURVE= 0.2663, 0.0339, 1.0000, 1.2969, 0.5000
SP-GROUP1= 0, 0, 0, 0,51P; SP-GROUP2= 0, 0, 0, 0,51P
SP-GROUP3= 0, 0, 0, 0,51P
Reading Logic Settings
The SL command is used to view the names of available logic schemes in memory. It also will return all of
the logic equations for a specific logic scheme.
SL Command
Purpose:
Obtain setting logic information.
Syntax:
SL[:<name>]
Comments: No password access is required to read settings.
Entering SL by itself returns all of the logic equations associated with the active logic scheme. Entering SL:
returns the names of all available logic schemes. Entering SL:<name> returns all logic equations and
settings for the named logic scheme.
SL Command Examples
1.
Read the logic schemes available in memory.
>SL:
USER, BASIC-OC, OC-W-79, OC-W-CTL, FDR-W-IL, BUS, BACKUP, NONE
2.
Read all logic settings associated with the BACKUP logic scheme.
>SL:BACKUP
SL-N:BACKUP
SL-50TP:1,0; SL-50TN:1,0; SL-50TQ:1,0
SL-150TP:1,0; SL-150TN:1,0; SL-150TQ:1,0
SL-51P:1,0
SL-51N:1,0
SL-51Q:1,0
SL-151N:0,0
SL-24:0,0
SL-25:0,0
SL-27P:0,0; SL-27X:0,0
SL-47:0,0
SL-59P:0,0; SL-59X:0,0
SL-81:0,0
SL-181:0,0
SL-281:0,0
SL-381:0,0
SL-481:0,0
SL-581:0,0
SL-62:0,0,0
Содержание BE1-951
Страница 157: ...BESTlogic Programmable Logic BE1 951 7 2 Figure 7 1 BESTlogic Function Blocks Courtesy of NationalSwitchgear com...
Страница 238: ...BE1 951 Human Machine Interface 10 5 Figure 10 5 Metering Menu Branch Structure Courtesy of NationalSwitchgear com...
Страница 239: ...10 6 Human Machine Interface BE1 951 Figure 10 6 Reports Menu Branch Structure Courtesy of NationalSwitchgear com...
Страница 270: ...12 2 Installation BE1 951 Figure 12 1 BE1 951 S1 Case Dimensions Courtesy of NationalSwitchgear com...
Страница 274: ...12 6 Installation BE1 951 Figure 12 5 BE1 951 H1 Case Dimensions Courtesy of NationalSwitchgear com...
Страница 283: ...BE1 951 Installation 12 15 Figure 12 16 Typical AC Connections Courtesy of NationalSwitchgear com...
Страница 394: ...A 18 Appendix BE1 951 Figure A 14 Time Characteristic Curve B Very Inverse 99 1376 Courtesy of NationalSwitchgear com...
Страница 396: ...A 20 Appendix BE1 951 Figure A 16 Time Characteristic Curve G Long Inverse 99 1622 Courtesy of NationalSwitchgear com...
Страница 397: ...BE1 951 Appendix A 21 Figure A 17 46 Time Characteristic Curve Courtesy of NationalSwitchgear com...