BE1-951
Testing and Maintenance
13-53
Mode 2 - On/Off
Step 1 Prepare for Mode 2 testing by transmitting the commands in Table 13-79 to the relay.
Table 13-79. x43 Mode 2 Test Commands
Command
Purpose
A=
Gain write access
SL-N=NONE
Zero out custom logic settings. Overwrite with
logic=none settings.
Y
Confirm overwrite
SL-N=MODE2
Sets MODE2 as custom logic name
SL-143=2
Sets 143 switch for Mode 2 operation
SL-VO1=143
Enables OUT1 to close for 143
EXIT;Y
Exit and save settings.
Step 2 Prepare to monitor the virtual switch operation. An ohmmeter or continuity tester may be used to
monitor the contact status of OUT1.
Step 3 Transmit the commands in Table 13-80 to the relay. These commands change the state of the 43
switch to On.
Result: OUT1 contact closes and remains closed.
Table 13-80. x43 Mode 2 On Commands
Command
Purpose
A=
Gain write access
CS-143=1
Selects 143 for On operation
CO-143=1
Executes 143 for On operation
Step 4
Transmit the commands in Table 13-81 to the relay. These commands change the state of the 143
switch to Off. It isn't necessary to gain access for the following steps unless the write access timer
expires.
Table 13-81. x43 Mode 2 Off Commands
Command
Purpose
CS-143=0
Selects 143 for Off operation
CO-143=0
Executes 143 for Off operation
Mode 3 - Pulse
Step 1 Prepare for Mode 3 testing by transmitting the commands in Table 13-82 to the relay.
Table 13-82. x43 Mode 3 Test Commands
Command
Purpose
A=
Gain write access
SL-N=NONE
Zero out custom logic settings. Overwrite with logic=none settings.
Содержание BE1-951
Страница 157: ...BESTlogic Programmable Logic BE1 951 7 2 Figure 7 1 BESTlogic Function Blocks Courtesy of NationalSwitchgear com...
Страница 238: ...BE1 951 Human Machine Interface 10 5 Figure 10 5 Metering Menu Branch Structure Courtesy of NationalSwitchgear com...
Страница 239: ...10 6 Human Machine Interface BE1 951 Figure 10 6 Reports Menu Branch Structure Courtesy of NationalSwitchgear com...
Страница 270: ...12 2 Installation BE1 951 Figure 12 1 BE1 951 S1 Case Dimensions Courtesy of NationalSwitchgear com...
Страница 274: ...12 6 Installation BE1 951 Figure 12 5 BE1 951 H1 Case Dimensions Courtesy of NationalSwitchgear com...
Страница 283: ...BE1 951 Installation 12 15 Figure 12 16 Typical AC Connections Courtesy of NationalSwitchgear com...
Страница 394: ...A 18 Appendix BE1 951 Figure A 14 Time Characteristic Curve B Very Inverse 99 1376 Courtesy of NationalSwitchgear com...
Страница 396: ...A 20 Appendix BE1 951 Figure A 16 Time Characteristic Curve G Long Inverse 99 1622 Courtesy of NationalSwitchgear com...
Страница 397: ...BE1 951 Appendix A 21 Figure A 17 46 Time Characteristic Curve Courtesy of NationalSwitchgear com...