BE1-951
Testing and Maintenance
13-61
D2843-12.vsd
02-02-99
0
1
0
1
0
1
B L K
INI
x 6 2
T i m e r
1 0 0 %
0 %
t1
t1
t2
t2
Figure 13-6. Mode 5 (Integrating Timer) Timing
Example
Step 2 Transmit the commands of Table 13-97 to the relay. These commands supply a block input to the
62 timer by changing the 43 switch state to TRUE.
NOTE
The CS and CO commands of Table 13-97 are performed three times. Follow the timing
sequence to illustrate timer mode action. The time delay settings may be increased if
difficulty is encountered with repeating the 43 switch actions.
Table 13-97. 62 Mode 5 Timer Initiate Commands
Command
Purpose
A=
Gain write access
CS-43=1
Selects 43 for TRUE operation
CO-43=1
Executes 43 TRUE operation
Wait no longer than 10 seconds to interrupt the T1 timer.
CS-43=0
Selects 43 for FALSE operation
CO-43=0
Executes 43 FALSE operation
Wait at least 5 seconds for the T2 timer to reset.
CS-43=0
Selects 43 for FALSE operation
CO-43=0
Executes 43 FALSE operation
Wait at least 20 seconds to allow the T1 timer to elapse.
EXIT
Exit the select and operate mode.
Step 3 Use the RS-LGC command to obtain an SER report and verify that the following actions were
logged. These events are illustrated in the timing diagram of Figure 13-6.
Timer T1 failed to time out in the first 43 switch action (TRUE).
Timer T2 timed out after the second 43 switch action (FALSE).
Timer T1 timed out and the 62 timer output went TRUE.
Timer T2 timed out and the 62 timer output returned to a FALSE state.
Step 4 (Optional) Repeat the 62 timer tests for Modes 1, 2, 3, and 5 for setting groups 1, 2, and 3.
Содержание BE1-951
Страница 157: ...BESTlogic Programmable Logic BE1 951 7 2 Figure 7 1 BESTlogic Function Blocks Courtesy of NationalSwitchgear com...
Страница 238: ...BE1 951 Human Machine Interface 10 5 Figure 10 5 Metering Menu Branch Structure Courtesy of NationalSwitchgear com...
Страница 239: ...10 6 Human Machine Interface BE1 951 Figure 10 6 Reports Menu Branch Structure Courtesy of NationalSwitchgear com...
Страница 270: ...12 2 Installation BE1 951 Figure 12 1 BE1 951 S1 Case Dimensions Courtesy of NationalSwitchgear com...
Страница 274: ...12 6 Installation BE1 951 Figure 12 5 BE1 951 H1 Case Dimensions Courtesy of NationalSwitchgear com...
Страница 283: ...BE1 951 Installation 12 15 Figure 12 16 Typical AC Connections Courtesy of NationalSwitchgear com...
Страница 394: ...A 18 Appendix BE1 951 Figure A 14 Time Characteristic Curve B Very Inverse 99 1376 Courtesy of NationalSwitchgear com...
Страница 396: ...A 20 Appendix BE1 951 Figure A 16 Time Characteristic Curve G Long Inverse 99 1622 Courtesy of NationalSwitchgear com...
Страница 397: ...BE1 951 Appendix A 21 Figure A 17 46 Time Characteristic Curve Courtesy of NationalSwitchgear com...