BE1-951
Metering
5-5
2.
Read the voltage across phases C and A.
>M-VCA
206V
M-VAR Command
Purpose:
Read metered 3 Phase Vars in primary units.
Syntax:
M-VAR[<phase>]
Comments: phase = 3/A/B/C
M-VAR Command Example
Read the system reactive power.
>M-VARA
-0.05KVAR
M-3V0 Command
Purpose:
Read metered voltage (V) in primary units
Syntax:
M-3VO
Comments: Reports “NA” unless VTP connection is 4-wire.
M-3V0 Command Example.
Read the zero-sequence voltage.
>M-3V0
0.30V
M-WATT Command
Purpose:
Read metered 3 Phase Watts (W) in primary units.
Syntax:
M-WATT[<phase>]
Comments: phase = 3/A/B/C
M-WATT Command Example
Read the system watts.
>M-WATTA
1.78KW
M-SYNC Command
Purpose:
Read metered sync angle between Phase and Aux inputs
Syntax : M-SYNC
M-SYNC Command Example
>M-SYNC
20.0 Deg
Содержание BE1-951
Страница 157: ...BESTlogic Programmable Logic BE1 951 7 2 Figure 7 1 BESTlogic Function Blocks Courtesy of NationalSwitchgear com...
Страница 238: ...BE1 951 Human Machine Interface 10 5 Figure 10 5 Metering Menu Branch Structure Courtesy of NationalSwitchgear com...
Страница 239: ...10 6 Human Machine Interface BE1 951 Figure 10 6 Reports Menu Branch Structure Courtesy of NationalSwitchgear com...
Страница 270: ...12 2 Installation BE1 951 Figure 12 1 BE1 951 S1 Case Dimensions Courtesy of NationalSwitchgear com...
Страница 274: ...12 6 Installation BE1 951 Figure 12 5 BE1 951 H1 Case Dimensions Courtesy of NationalSwitchgear com...
Страница 283: ...BE1 951 Installation 12 15 Figure 12 16 Typical AC Connections Courtesy of NationalSwitchgear com...
Страница 394: ...A 18 Appendix BE1 951 Figure A 14 Time Characteristic Curve B Very Inverse 99 1376 Courtesy of NationalSwitchgear com...
Страница 396: ...A 20 Appendix BE1 951 Figure A 16 Time Characteristic Curve G Long Inverse 99 1622 Courtesy of NationalSwitchgear com...
Страница 397: ...BE1 951 Appendix A 21 Figure A 17 46 Time Characteristic Curve Courtesy of NationalSwitchgear com...