Output
Purpose
Output Description
Variable
Label
State Labels
TRUE (1)
FALSE (0)
BE1-951
Application
8-39
VO13
Feeder Backup Mode
Alarm.
TRUE when in Setting Group 1.
FEEDER_BU
BACKUP
NORMAL
BESTlogic Expression: VO13 = SG1
VO14
Not Used
VO14
TRUE
FALSE
BESTlogic Expression: VO14 = 0
VO15
Test Mode.
Blocks the BFI signal (VO3) to an
external breaker failure relay.
TRUE when IN4 de-energizes or
virtual switch 343 closes.
TEST_MODE
TEST
NORMAL
BESTlogic Expression: VO15 = /IN4+343
Содержание BE1-951
Страница 157: ...BESTlogic Programmable Logic BE1 951 7 2 Figure 7 1 BESTlogic Function Blocks Courtesy of NationalSwitchgear com...
Страница 238: ...BE1 951 Human Machine Interface 10 5 Figure 10 5 Metering Menu Branch Structure Courtesy of NationalSwitchgear com...
Страница 239: ...10 6 Human Machine Interface BE1 951 Figure 10 6 Reports Menu Branch Structure Courtesy of NationalSwitchgear com...
Страница 270: ...12 2 Installation BE1 951 Figure 12 1 BE1 951 S1 Case Dimensions Courtesy of NationalSwitchgear com...
Страница 274: ...12 6 Installation BE1 951 Figure 12 5 BE1 951 H1 Case Dimensions Courtesy of NationalSwitchgear com...
Страница 283: ...BE1 951 Installation 12 15 Figure 12 16 Typical AC Connections Courtesy of NationalSwitchgear com...
Страница 394: ...A 18 Appendix BE1 951 Figure A 14 Time Characteristic Curve B Very Inverse 99 1376 Courtesy of NationalSwitchgear com...
Страница 396: ...A 20 Appendix BE1 951 Figure A 16 Time Characteristic Curve G Long Inverse 99 1622 Courtesy of NationalSwitchgear com...
Страница 397: ...BE1 951 Appendix A 21 Figure A 17 46 Time Characteristic Curve Courtesy of NationalSwitchgear com...