BE1-951
Installation
12-29
Notes:
°
1.
The neutral ground (I
N
) operates on internally calculated residual (3Io) current (VXIN)
2.
VTP connections shown are for H1 case. See Figure 12-13 for S1 case connections
3.
3-wire connection shown. See Figure 12-20 for alternate VTP connections. A 4-wire
connection provides negative sequence and, if selected, zero sequence voltage polarizing
(V0IN or V0IG) for ground faults; 3-wire connection provides negative sequence voltage
polarizing.
4.
CT polarity connected to relay polarity, power flow from Bus to Line defined as power out
and = “+” watts; OC elements set for forward trip
5.
VX connected to external source of 3E
0
polarizing voltage.
Figure 12-32. Directional Ground OC Protection Using External Source of Zero Sequence Polarizing
Voltage (VX) Compared to Calculated Residual (3IO) (IN)
Содержание BE1-951
Страница 157: ...BESTlogic Programmable Logic BE1 951 7 2 Figure 7 1 BESTlogic Function Blocks Courtesy of NationalSwitchgear com...
Страница 238: ...BE1 951 Human Machine Interface 10 5 Figure 10 5 Metering Menu Branch Structure Courtesy of NationalSwitchgear com...
Страница 239: ...10 6 Human Machine Interface BE1 951 Figure 10 6 Reports Menu Branch Structure Courtesy of NationalSwitchgear com...
Страница 270: ...12 2 Installation BE1 951 Figure 12 1 BE1 951 S1 Case Dimensions Courtesy of NationalSwitchgear com...
Страница 274: ...12 6 Installation BE1 951 Figure 12 5 BE1 951 H1 Case Dimensions Courtesy of NationalSwitchgear com...
Страница 283: ...BE1 951 Installation 12 15 Figure 12 16 Typical AC Connections Courtesy of NationalSwitchgear com...
Страница 394: ...A 18 Appendix BE1 951 Figure A 14 Time Characteristic Curve B Very Inverse 99 1376 Courtesy of NationalSwitchgear com...
Страница 396: ...A 20 Appendix BE1 951 Figure A 16 Time Characteristic Curve G Long Inverse 99 1622 Courtesy of NationalSwitchgear com...
Страница 397: ...BE1 951 Appendix A 21 Figure A 17 46 Time Characteristic Curve Courtesy of NationalSwitchgear com...