8-38
Application
BE1-951
Table 8-20. BUS Virtual Output Logic
Output
Purpose
Output Description
Variable
Label
State Labels
TRUE (1)
FALSE (0)
VOA
(OUTA)
Alarm Output Contact
Alarm contact closes automatically
when relay trouble alarm occurs.
ALARM
ACTIVE
NORMAL
BESTlogic Expression: VOA = 0
VO1
(OUT1)
Bus Breaker Trip.
Trip for bus breaker virtual control
switch trip OR for 51 trip when in
Normal mode.
BKR_TRIP
TRIP
NORMAL
BESTlogic Expression: VO1 = 101T+VO8*SG0
VO2
(OUT2)
Bus Breaker Close.
Close breaker when virtual breaker
control switch is operated to close.
BKR_CLOSE
CLOSE
NORMAL
BESTlogic Expression: VO2 = 101C
VO3
(OUT3)
External Breaker
Failure Relay BFI.
Initiate external Breaker Failure
Relay for Bus Timed-Overcurrent
trip when in Normal mode.
EXT-BFI-O3
BFI
NORMAL
BESTlogic Expression: VO3 = VO8*SG0*/VO15
VO4
(OUT4)
Bus Fault Trip (86B).
Trip bus breaker for bus faults
(50TPT, 50TNT, or 50TQT) when in
Normal mode.
BUS_TRIP
TRIP
NORMAL
BESTlogic Expression: VO4 = VO9*SG0
VO5
(OUT5)
Feeder Breaker Trip.
Trip feeder breaker via auxiliary
relay (94) for timed (51) or
instantaneous (50) trip when in
Feeder Relay Backup mode.
FEEDER_TRIP
TRIP
NORMAL
BESTlogic Expression: VO5 = VO11*SG1
VO6
Not Used
VO6_LABEL
TRUE
FALSE
BESTlogic Expression: VO6 = 0
VO7
Not Used
VO7_LABEL
TRUE
FALSE
BESTlogic Expression: VO7 = 0
VO8
Time-Overcurrent Trip
TRUE when any time overcurrent
element trips.
51_TRIP
TRIP
NORMAL
BESTlogic Expression: VO8 = 51PT+51NT+51QT
VO9
Instantaneous
Overcurrent Trip
TRUE when any instantaneous
overcurrent element trips.
50_TRIP
TRIP
NORMAL
BESTlogic Expression: VO9 = 50TPT+50TNT+50TQT
VO10
Not Used
VO10
TRUE
FALSE
BESTlogic Expression: VO10 = 0
VO11
Protective Trip
Expression.
TRUE when any 50 or 51 element
has picked up.
PROT_TRIP
TRIP
NORMAL
BESTlogic Expression: VO11 = 50TPT+50TNT+50TQT+51PT+51NT+51QT
VO12
Protection Picked Up
Expression.
TRUE when any 50 or 51 element
has picked up.
PROT_PU
PU
NORMAL
BESTlogic Expression: VO12 = 51PPU +51NPU+51QPU
Содержание BE1-951
Страница 157: ...BESTlogic Programmable Logic BE1 951 7 2 Figure 7 1 BESTlogic Function Blocks Courtesy of NationalSwitchgear com...
Страница 238: ...BE1 951 Human Machine Interface 10 5 Figure 10 5 Metering Menu Branch Structure Courtesy of NationalSwitchgear com...
Страница 239: ...10 6 Human Machine Interface BE1 951 Figure 10 6 Reports Menu Branch Structure Courtesy of NationalSwitchgear com...
Страница 270: ...12 2 Installation BE1 951 Figure 12 1 BE1 951 S1 Case Dimensions Courtesy of NationalSwitchgear com...
Страница 274: ...12 6 Installation BE1 951 Figure 12 5 BE1 951 H1 Case Dimensions Courtesy of NationalSwitchgear com...
Страница 283: ...BE1 951 Installation 12 15 Figure 12 16 Typical AC Connections Courtesy of NationalSwitchgear com...
Страница 394: ...A 18 Appendix BE1 951 Figure A 14 Time Characteristic Curve B Very Inverse 99 1376 Courtesy of NationalSwitchgear com...
Страница 396: ...A 20 Appendix BE1 951 Figure A 16 Time Characteristic Curve G Long Inverse 99 1622 Courtesy of NationalSwitchgear com...
Страница 397: ...BE1 951 Appendix A 21 Figure A 17 46 Time Characteristic Curve Courtesy of NationalSwitchgear com...