NSTALLATION

 

AND

 O

PERATION

 M

ANUAL

 

    GROUND-FAULT   

                   

PROTECTION DEVICE 

       600V MODEL 

Содержание GFPD-600V

Страница 1: ...For the most recent manual updates please visit our website e mail info morningstarcorp com website www morningstarcorp com INSTALLATION AND OPERATION MANUAL GROUND FAULT PROTECTION DEVICE 600V MODEL...

Страница 2: ...3 1 3 Vertical Mounting 9 3 1 4 Stand Alone Use 10 3 2 0 Wiring the GFPD 600V Box 10 3 2 1 Pre Wired GFPD 600V Breaker Assembly 10 3 2 2 Completing Wiring 10 4 0 GFPD 600V Operation 14 4 1 Ground Fau...

Страница 3: ...de fuite la terre Les symboles suivants sont utili s s tout au long de ce manuel pour indiquer des conditions potentiellement dangereuses ou des consignes de s curit importantes WARNING Indicates a p...

Страница 4: ...ns ad quates Quand remplacer l utilisation de piles correctement sp cifi tailles types et cotes fond es sur l application et conception des syst mes PRUDENCE limination appropri e des batpiles est n c...

Страница 5: ...hock do not perform any service other than that specified in the operating instructions unless you are qualified to do so AVERTISSEMENT Pour r duire le risque de choc lec trique n effectuez aucune op...

Страница 6: ...ion Safety Precautions Mount the GFPD 600V indoors Prevent exposure to the elements and do not allow water to enter the device Use insulated tools when working with batteries Avoid wearing jewelry dur...

Страница 7: ...Connexions d alimentation doivent rester serr es pour viter un chauffement excessif d une mauvaise connexion Utilisez la bonne taille des conducteurs The GFPD 600V must be installed by a qualified tec...

Страница 8: ...courant continu Le GFPD 600V doit tre install par un technicien quali fi conform ment la r glementation lectrique du pays o le produit est install l aide de la cosse de terre dans le compartiment de c...

Страница 9: ...es 2 0 DIMENSIONS AND FEATURES 14 05 in 357 mm 8 70 in 221 mm 4 16in 106mm Ganged Breakers Bi color LED red and green Test Reset Button Four Power Termination Connections underside Conduit Wire Knock...

Страница 10: ...oller in several ways A suggested mounting configuration is with the GFPD 600V box to the left of the vertically mounted controller as shown in Figure 3 with the two small knock outs and one large kno...

Страница 11: ...or mounting instructions and install 2 Align GFPD 600V box in desired position and mark the four 4 corner mounting hole locations through the wiring box Remove the GFPD box 3 Drill 3 32 2 5 mm holes a...

Страница 12: ...e assembled at the fac tory Feedback jumper shunt and trip signal leads are pre wired to the GFPD 600V terminals See Figure 6 The GFPD 600V external voltage source connections are described in the nex...

Страница 13: ...If using a Standard Box Figure 7 connect and controller battery wires directly to controller s and bat tery terminal lugs If using a DB model controller see note in Step 8 Step 8 Wire controller batt...

Страница 14: ...minals NOTE Do not tap from a lower voltage battery bank section that is part of a higher voltage bank an imbalance will occur Step 10 Ground the PV system properly by electrically connecting each ind...

Страница 15: ...ulated 600V 10 32 ring terminal typ of 2 1 Trip Signal Wire from each breaker typ of 2 no polarity Feedback Jumper typ of 2 no polarity Terminated with insulated 600V 10 32 ring terminal typ of 4 3 4...

Страница 16: ...ration can be restored Any current imbalance between the and con ductors of a circuit indicates a ground fault Morningstar s GFPD 600V will detect this condition and break the circuit on both the and...

Страница 17: ...rred pressing the test button resets the GFPD 600V to the normal condition 4 2 LED Indications and Audible Warnings A bi color LED and buzzer indicate operating status a ground fault event module wiri...

Страница 18: ...correct wiring error and or close breaker Push the test button to resume normal operation When the low battery voltage threshold of nine volts is reached the buzzer will sound To resume normal opera...

Страница 19: ...LED RED SOLID BUZZER GF ERROR LED RED FLASHING BUZZER LOW BATTERY BUZZER TEST BUTTON PRESSED TEST BUTTON PRESSED START UP SEQUENCE LED THREE GREEN FLASHES TEST BUTTON PRESSED System Test GROUND FAULT...

Страница 20: ...r will pay the return shipping charges if the repairs are cov ered under the warranty WARRANTY EXCLUSIONS AND LIMITATIONS This warranty does not apply under the following conditions Damage by accident...

Страница 21: ...79 in 20 0 mm Breaker Power Posts 1 4 in 20 Studs Recommended Breaker Power Post Nut Torque 30 35 in lb 3 4 4 Nm Recommended GFPD 600V Sensing Unit Terminal Torque 3 5 in lb 0 4 Nm GFPD 600V Sensing...

Страница 22: ...o 85 C Humidity Tolerance Up to 100 Tropicalization PCB Conformal Coating CERTIFICATIONS Meets U S NEC 690 5 and 690 35 c requirements for use as a GFPD ETL Listed to UL 1741 and CSA C22 2 No 107 1 01...