50TQ
Requires 18-20 cycle coordination delay since no
blocking is provided for feeder relay pickup. Used for
backup bus fault trip.
0
1
(enabled)
150TP
Used for fault detector supervision of external BFI.
Since this isn’t used for tripping, the SG-TARG
command should not be used to enable this function.
0
1
(enabled)
150TN
Used for fault detector supervision of external BFI.
Since this isn’t used for tripping, the SG-TARG
command should not be used to enable this function.
0
1
(enabled)
150TQ
Used for fault detector supervision of external BFI.
Since this isn’t used for tripping, the SG-TARG
command should not be used to enable this function.
0
1
(enabled)
51P
Not used
0
1 (enabled)
51N
Not used
0
1 (enabled)
51Q
Not used
0
1 (enabled)
151N
Not used
0
0 (disabled)
27P
Not used
0
0 (disabled)
59P
Not used
0
0 (disabled)
59X
Not used
0
0 (disabled)
47
Not used
0
0 (disabled)
62
Not used
0
0 (disabled)
162
Not used
0
0 (disabled)
79
Not used
0
0 (disabled)
81
Not used
0
0 (disabled)
181
Not used
0
0 (disabled)
281
Not used
0
0 (disabled)
381
Not used
0
0 (disabled)
481
Not used
0
0 (disabled)
581
Not used
0
0 (disabled)
BF
Breaker Fail Initiate Logic: Initiate breaker failure when
breaker failure initiate expression is TRUE.
VO10
1
(enabled)
Block Input Logic: Block breaker failure protection when
relay is in Test mode.
VO15
GROUP
Input 0 Logic: Switch to Setting Group 1 if feeder relay is
out of service (indicated by open contact from feeder
relays).
IN3
2
(binary coded
selection)
Input 1 Logic: Not used
0
N/A
Input 2 Logic: Not used
0
N/A
Input 3 Logic: Not used
0
N/A
Auto/Manual Logic: Auto/Manual switch fixed in Manual
position. No automatic selection. Selection by contact
sensing only.
0
N/A
Содержание BE1-951
Страница 157: ...BESTlogic Programmable Logic BE1 951 7 2 Figure 7 1 BESTlogic Function Blocks Courtesy of NationalSwitchgear com...
Страница 238: ...BE1 951 Human Machine Interface 10 5 Figure 10 5 Metering Menu Branch Structure Courtesy of NationalSwitchgear com...
Страница 239: ...10 6 Human Machine Interface BE1 951 Figure 10 6 Reports Menu Branch Structure Courtesy of NationalSwitchgear com...
Страница 270: ...12 2 Installation BE1 951 Figure 12 1 BE1 951 S1 Case Dimensions Courtesy of NationalSwitchgear com...
Страница 274: ...12 6 Installation BE1 951 Figure 12 5 BE1 951 H1 Case Dimensions Courtesy of NationalSwitchgear com...
Страница 283: ...BE1 951 Installation 12 15 Figure 12 16 Typical AC Connections Courtesy of NationalSwitchgear com...
Страница 394: ...A 18 Appendix BE1 951 Figure A 14 Time Characteristic Curve B Very Inverse 99 1376 Courtesy of NationalSwitchgear com...
Страница 396: ...A 20 Appendix BE1 951 Figure A 16 Time Characteristic Curve G Long Inverse 99 1622 Courtesy of NationalSwitchgear com...
Страница 397: ...BE1 951 Appendix A 21 Figure A 17 46 Time Characteristic Curve Courtesy of NationalSwitchgear com...