BE1-951
Protection and Control
4-29
SL-27P and SL-59P Command Examples
1.
Read the 27 phase logic settings.
>SL-27P
2,0
(These settings indicate that undervoltage on two or more phases is
required to initiate pickup and blocking isn’t used.)
2.
Program the 59P logic so that overvoltage on all three phases is required to initiate pickup. Block the
59 function when input 4 is closed (TRUE) or when virtual output 6 is TRUE.
>SL-59P=3,IN4+VO6
Operating Settings for Undervoltage and Overvoltage Elements
Operating settings for the 27P and 59P functions consist of pickup and time delay values. The pickup value
determines the level of voltage required for the element to start timing toward a trip. The time delay value
determines the length of time between pickup and trip. Time delays can be set in milliseconds, seconds, or
cycles. The default is milliseconds if no unit of measure is specified. A time setting of zero makes the
element instantaneous with no intentional time delay. Phase undervoltage settings are made using the
S<g>-27 command. Phase overvoltage settings are made using the S<g>-59P command. The unit of
measure for the pickup setting is secondary volts (PP or PN) and depends on the SG-VTP setting. For more
information, refer to Section 3,
Input and Output Functions, Voltage Inputs. Settings can also be viewed or
changed at the front panel HMI using screens 5.x.3.1 (phase undervoltage) and 5.x.7.1 (3 phase
overvoltage), where x equals 1 for setting group 0, 2 for setting group 1, 3 for setting group 2, and 4 for
setting group 3. Undervoltage and overvoltage operating settings are summarized in Table 4-21.
Table 4-21. Undervoltage and Overvoltage Operating Settings
Setting
Range
Increment
Unit of
Measure
Default
Pickup
0 = disabled
10 to 300
0.1 (for 0 - 99.9)
1.0 (for 100 - 300)
secondary
volts
#
0
Time Delay
50 to 999 milliseconds
1
milliseconds
50
0.1 to 600 seconds
0.1 for 0.1 to 9.9
seconds
1.0 for 10 to 600
seconds
0 to 36,000 cycles (60 Hz)
9
cycles
0 to 30,000 cycles (50 Hz)
9
Time delays less than 10 cycles can be entered to the nearest 0.1 cycle from the front panel
HMI. All time delays can be entered to the nearest 0.01 cycle from the ASCII command interface.
Time delays entered in cycles are converted to milliseconds or seconds. Increment precision after
conversion is limited to that appropriate for each of those units of measure.
# Unit of measure is secondary VPP or secondary VPN depending on the VTP connection settings.
S<g>-27P and S<g>-59P Commands
Purpose:
Read or set protection settings for the phase undervoltage and overvoltage functions.
Syntax:
S<g>-27P or S<g>-59P[=<Pickup>,<Time Delay>]
Comments: g = setting group 0, 1, 2, or 3. Use # as a wildcard to read or change all groups. See Table 4-
21 for S<g>-27P and S<g>-59P settings information.
S<g>-27P and S<g>-59P Command Examples
1.
Set the group 0 phase undervoltage setting at 80 volts and the time delay at zero.
>S0-27P=80,0
2.
Set the phase overvoltage pickup at 135 volts and the time delay at 3 seconds for all setting groups.
>S#-59P=135,3s
Содержание BE1-951
Страница 157: ...BESTlogic Programmable Logic BE1 951 7 2 Figure 7 1 BESTlogic Function Blocks Courtesy of NationalSwitchgear com...
Страница 238: ...BE1 951 Human Machine Interface 10 5 Figure 10 5 Metering Menu Branch Structure Courtesy of NationalSwitchgear com...
Страница 239: ...10 6 Human Machine Interface BE1 951 Figure 10 6 Reports Menu Branch Structure Courtesy of NationalSwitchgear com...
Страница 270: ...12 2 Installation BE1 951 Figure 12 1 BE1 951 S1 Case Dimensions Courtesy of NationalSwitchgear com...
Страница 274: ...12 6 Installation BE1 951 Figure 12 5 BE1 951 H1 Case Dimensions Courtesy of NationalSwitchgear com...
Страница 283: ...BE1 951 Installation 12 15 Figure 12 16 Typical AC Connections Courtesy of NationalSwitchgear com...
Страница 394: ...A 18 Appendix BE1 951 Figure A 14 Time Characteristic Curve B Very Inverse 99 1376 Courtesy of NationalSwitchgear com...
Страница 396: ...A 20 Appendix BE1 951 Figure A 16 Time Characteristic Curve G Long Inverse 99 1622 Courtesy of NationalSwitchgear com...
Страница 397: ...BE1 951 Appendix A 21 Figure A 17 46 Time Characteristic Curve Courtesy of NationalSwitchgear com...