2052
32
CUB1
4
Block ON
2053
32
CUB1
5
Block OFF
2112
33
CUB2
0
Start ON
2113
33
CUB2
1
Start OFF
2114
33
CUB2
2
Trip ON
2115
33
CUB2
3
Trip OFF
2116
33
CUB2
4
Block ON
2117
33
CUB2
5
Block OFF
2176
34
CUB3
0
Start ON
2177
34
CUB3
1
Start OFF
2178
34
CUB3
2
Trip ON
2179
34
CUB3
3
Trip OFF
2180
34
CUB3
4
Block ON
2181
34
CUB3
5
Block OFF
2240
35
CUB4
0
Start ON
2241
35
CUB4
1
Start OFF
2242
35
CUB4
2
Trip ON
2243
35
CUB4
3
Trip OFF
2244
35
CUB4
4
Block ON
2245
35
CUB4
5
Block OFF
In the register of the CUB function recorded events are start, trip or blocked “On” event process data.
Table below presents the structure of CUB function register content. This information is available in 12
last recorded events for all provided instances separately.
Table. 5.4.5. - 80. Register content
Date & Time
Event
code
Fault
type
Trigger
current
Fault
current
Prefault
current
Fault
currents
Trip time
remaining
Used
SG
dd.mm.yyyy
hh:mm:ss.mss
2048-
2245
Descr.
Unbalance
Start
average
current
Trip -20ms
averages
Start -200ms
averages
I1,I2,IZ mag.
and ang.
0ms -1800s
1 – 8
5.4.6. Harmonic overcurrent Ih> (50H/51H/68H)
Harmonic overcurrent function (HOC) is used for non-directional instant- and time delayed harmonic
overcurrent detection and clearing for various applications including feeder, lter and machine
applications of utilities and industry. The number of available instances of the function depends of the
IED model. Function measures constantly selected measurement channels selected harmonic
component either on absolute value or relative to the fundamental frequency component. Blocking
signal and setting group selection controls the operating characteristics of the function during normal
operation.
Outputs of the function are Start Trip and Blocked signals. Setting parameters are static inputs for the
function which are changed only by user input in the setup phase of the function. Non directional
overcurrent function utilizes total of eight separate setting groups which can be selected from one
common source.
AQ-T257
Instruction manual
Version: 2.00
71