No/Light
load
0:Not
active
1:Active
1
0
Signal is active, when the TRF function detects current below “No load current”.
This signal presents situation when there is very light load or only one or neither
side of trafo is energized.
HV side
inrush
detected
0:Not
active
1:Active
1
0
Signal is active, when the detected current rises over the “High overcurrent” limit
in the HV side.
LV side
inrush
detected
0:Not
active
1:Active
1
0
Signal is active, when the detected current rises over the “High overcurrent” limit
in the LV side.
Load
normal
0:Not
active
1:Active
1
0
Signal is active when the measured current is below nominal and over no load
limit current.
Overloading
0:Not
active
1:Active
1
0
Signal is active when the measured current is in between nominal and high
overcurrent limits.
HVY
Overloading
0:Not
active
1:Active
1
0
Signal is active when the measured current is over high overcurrent limit.
Events
TRF function generates events from detected transformer energizing status. From changes of the
events also data register is available.
Table. 5.4.16. - 140. Event codes of the TRF function
Event Number
Event channel
Event block name
Event Code
Description
4608
72
TRF1
0
Light/No load On
4609
72
TRF1
1
Light/No load Off
4610
72
TRF1
2
HV side inrush On
4611
72
TRF1
3
HV side inrush Off
4612
72
TRF1
4
LV side inrush On
4613
72
TRF1
5
LV side inrush Off
4614
72
TRF1
6
Load normal On
4615
72
TRF1
7
Load normal Off
4616
72
TRF1
8
Overloading On
4617
72
TRF1
9
Overloading Off
4618
72
TRF1
10
High overload On
4619
72
TRF1
11
High overload Off
4620
72
TRF1
12
Setting changes, calculating new trafo data
4621
72
TRF1
13
Calculation nished, possible restart
In the table below is presented the structure of TRF function register content. This information is
available in 12 last recorded events.
Table. 5.4.16. - 141. Register content.
Date & Time
Event
code
HVL1 current
HVL2
current
HVL3
current
LVL1
current
LVL2
current
LVL3
current
dd.mm.yyyy
hh:mm:ss.mss
4608-
4621
Descr.
HV side Phase L1
current xIn
HV side
Phase L2
current xIn
HV side
Phase L3
current xIn
LV side
Phase L1
current xIn
LV side
Phase L2
current xIn
LV side
Phase L3
current xIn
AQ-T257
Instruction manual
Version: 2.00
© Arcteq Relays Ltd
134