Tap changer on low
border
Indication if the tap changer has reached minimum voltage
low position
0:No
1:Yes
-
0:No
Control settings
Control settings de ne the control model and manual raise and lower commands from the HMI. Control
outputs timing control is here as well.
Table. 5.5.1. - 175. Control settings parameters.
Name
Description
Range
Step
Default
Control mode
Selection of control mode
0: Auto
1: Manual
-
0:Auto
Manual tap increase Increase tap by 1 step to higher voltage
0:-
1:Increase
-
0:-
Manual tap
decrease
Decrease tap by 1 step to lower voltage
0:-
1:Decrease
-
0:-
Control pulselength
max
Maximum time the tap control (up or down) output contact can
be closed
0.000…
1800.000s
0.005s 2.000s
Control pulselength
min
Minimum time the tap control (up or down) output contact
should be closed.
0.000…
1800.000s
0.005s 2.000s
Min time between
pulses
Minimum time in between of separate consecutive control
commands
0.000…
1800.000s
0.005s 0.500s
Tab settings
In tap settings the tap changer equipment properties and connection for position indication to AVR are
set.
Table. 5.5.1. - 176. Tap settings parameters.
Name
Description
Range
Step
Default
Tap
position
indication
Selection of tap position indication
message.
0: Select
1: mA input 7
2: mA input 8
3: mA External input (ADAM)
4: Scaled input
5: BCD coded inputs
-
0: Select
Tap steps
totally
Number of tap steps from minimum
to maximum
1…70
1
18
Tap
center
location
Position of nominal non regulated tap
location
1…35
1
9
Tap step
effect
Effect of one tap step in percentage
of nominal voltage
0.01…10.00%
0.01%
1.67%
Tap
position
indication
De nes if mA minimum or maximum
value is the highest tap position.
1:Max.mA.max.Pos.2:Min.mA.max.Pos -
1:Max.mA.max.Pos
mA input
low range
mA input measurement presenting
the minimum tap position. Setting is
visible if any of the mA position
indication modes are selected.
0.000…4.000mA
0.001mA 4.000mA
mA input
high
range
mA input measurement presenting
the maximum tap position. Setting is
visible if any of the mA position
indication modes are selected.
0.010…20.000mA
0.001mA 4.000mA
AQ-T257
Instruction manual
Version: 2.00
225
© Arcteq Relays Ltd