In the following table are presented the setting parameters for the function time characteristics.
Table. 5.6.6. - 226. Operating time characteristics setting parameters.
Name
Range
Step
Default
Description
Tpha
0.000…
1800.000s
0.005s 10.000s Delay time setting for the alarm timer from the phase currents measured
THD.
TI01
0.000…
1800.000s
0.005s 10.000s Delay time setting for the alarm timer from the residual current I01
measured THD.
TI02
0.000…
1800.000s
0.005s 10.000s Delay time setting for the alarm timer from the residual current I02
measured THD.
Events and registers
The THD function generates events and registers from the status changes of the alarm function when it
is activated. Recorded signals are Start and Alarm signals per monitoring element and common
blocked signals. To main event buffer is possible to select status “On” or “Off” messages.
In the function is available 12 last registers where the triggering event of the function (THD start, alarm
or blocked) is recorded with time stamp and process data values.
Table. 5.6.6. - 227. Event codes of the THD function
Event Number
Event channel
Event block name
Event Code
Description
3520
55
THD1
0
THD Start Phase On
3521
55
THD1
1
THD Start Phase Off
3522
55
THD1
2
THD Start I01 On
3523
55
THD1
3
THD Start I01 Off
3524
55
THD1
4
THD Start I02 On
3525
55
THD1
5
THD Start I02 Off
3526
55
THD1
6
THD Alarm Phase On
3527
55
THD1
7
THD Alarm Phase Off
3528
55
THD1
8
THD Alarm I01 On
3529
55
THD1
9
THD Alarm I01 Off
3530
55
THD1
10
THD Alarm I02 On
3531
55
THD1
11
THD Alarm I02 Off
3532
55
THD1
12
Blocked On
3533
55
THD1
13
Blocked Off
In the register of the THD function is recorded activated, blocked etc. “On” event process data. In the
table below is presented the structure of THD function register content. This information is available in
12 last recorded events for all provided instances separately.
Table. 5.6.6. - 228. Register content.
Date & Time
Event
code
IL1
THD
IL2
THD
IL3
THD
I01
THD
I02
THD
Ph
Trem
I01
Trem
I02
Trem
Used
SG
dd.mm.yyyy
hh:mm:ss.mss
3521-3534
Descr.
Measured THD values on the trigger event.
Time left to Alarm on the
trigger event
1 - 8
AQ-T257
Instruction manual
Version: 2.00
© Arcteq Relays Ltd
286