Blocking signal can be tested also in the commissioning phase of the stage by software switch signal
when relay common and global testing mode is activated. User settable variables are binary signals
from the system.
Setting parameters
Table. 5.5.5. - 195. General settings of the synchrocheck function
Name
Range Step Default
Description
Use SYN1,2,3
No
Yes
-
No
Activation of individual stages of the synchrocheck function. Activation of a
stage reveals the parameter settings for con guration.
SYN1 (U4) V
Reference
Not in
use
UL12
UL23
UL31
UL1
UL2
UL3
-
Not in
use
- Choose the reference voltage of the stage.
- In 3LN+U4 and 2LL+U0+U4 mode all references are available.
- In 3LL+U4 and 2LL+U3+U4 mode UL12, UL23 and UL31 references are
available
SYN2 (U3) V
Reference
Not in
use
UL12
UL23
UL31
UL1
UL2
UL3
-
Not in
use
- Choose the reference voltage of the stage.
- In 2LL+U3+U0 mode all references are available
- In 2LL+U3+U4 mode UL12, UL23 and UL31 are available
SYN3
Reference
Not in
use
U3-U4
-
Not in
use
- Choose if SYN3 stage is activated or disabled
- Operable in 2LL+U3+U4 mode
- UL12, UL23 and UL31 references are available
Table. 5.5.5. - 196. Synchrocheck stage settings
Name
Range
Step
Default
Description
SYN U conditions
LL only
LL & LD
LL & DL
LL & DD
LL & LD & DL
LL & LD & DD
LL & DL & DD
Bypass
-
LL only
Allowed states of the supervised systems.
SYN U live >
0.10…120.00%Un 0.01%Un 20%Un
Voltage limit of the live state
SYN U dead <
0.10…120.00%Un 0.01%Un 20%Un
Voltage limit of the dead state
SYN U diff <
0.00…120.00%Un 0.01%Un 2%Un
Maximum allowed voltage difference between the systems.
SYN angle diff <
0.00…90.00deg
0.01deg
0.5deg
Maximum allowed angle difference between the systems.
SYN freq diff <
0.00…0.50Hz
0.01Hz
0.1Hz
Maximum allowed frequency difference between the systems.
NOTE! Remember to set a voltage channel (U3 or U4) into synchrocheck mode in the voltage
transformer settings (
Measurements
→
VT Module
).
Events and registers
The synchrocheck function generates events and registers from the status changes like syn ok, bypass
and blocked. To main event buffer is possible to select status “On” or “Off” messages. The
synchrocheck function offers three independent instances which events are segregated for each
instance operation.
AQ-T257
Instruction manual
Version: 2.00
© Arcteq Relays Ltd
250