t = Operating time
I
2meas
= Calculated negative sequence
I
N
= Nominal current
k = Constant k value (user settable delay multiplier)
I
set
= Pick-up setting of the function
Figure. 5.4.5. - 27. Operation characteristics curve for I2 > Curve2
Following table presents the setting parameters for the function time characteristics.
Table. 5.4.5. - 77. Operating time characteristics setting parameters.
Name
Range
Step
Default
Description
Delay Type
DT
IDMT
-
DT
Selection of the delay type time counter. Selection possibilities are
dependent (IDMT, Inverse De nite Minimum Time) and
independent (DT, De nite Time) characteristics.
De nite
operating time
delay
0.000...1800.000s 0.005s 0.040s
De nite time operating delay. Setting is active and visible when
Delay Type is selected to DT.
When set to 0.000 s the stage operates as instant (PIOC, 50)
stage without added delay. When the parameter is set to 0.005 –
1800 s the stage operates as independent delayed (PTOC, 51).
Delay curve
series
IEC
IEEE
Non-standard
-
IEC
Setting is active and visible when Delay Type is selected to IDMT.
Delay curve series for IDMT operation following either IEC or
IEEE/Ansi standard de ned characteristics. Non-standard
characteristics include delay curves outside of the two sandards.
Delay
characteristics
IEC
NI
EI
VI
LTI
Param
-
NI
Setting is active and visible when Delay Type is selected to IDMT.
IEC standard delay characteristics. Normally Inverse, Extremely
Inverse, Very Inverse and Long Time Inverse characteristics.
Param selection allows the tuning of the constants A and B which
allows setting of characteristics following the same formula as the
IEC curves mentioned here.
Delay
characteristics
IEEE
LTI
LTVI
LTEI
MI
VI
EI
STI
STEI
Param
-
LTI
Setting is active and visible when Delay Type is selected to IDMT.
IEEE standard delay characteristics. Long Time Inverse, Long Time
Very Inverse, Long Time Extremely Inverse, Moderately Inverse,
Very Inverse, Extremely Inverse, Short Time Inverse, Short Time
Extremely Inverse characteristics. Param selection allows the
tuning of the constants A, B and C which allows setting of
characteristics following the same formula as the IEEE curves
mentioned here.
AQ-T257
Instruction manual
Version: 2.00
69
© Arcteq Relays Ltd