Reset
Reset ratio
97 / 103 % of pickup voltage setting
Reset time setting
Inaccuracy: Reset time
0.010 … 10.000 s, step 0.005 s
±2.0 % or ±80 ms
Instant reset time and start-up reset
<50 ms
VTS MCB trip bus/line (external input)
<50 ms
Note!
When turning on auxiliary power of IED the normal condition of stage has to be ful lled before
tripping.
9.2.3.3. Disturbance recorder (DR)
Table. 9.2.3.3. - 288. Disturbance recorder (DR) technical data
Recorded values
Recorder analogue
channels
0…9 channels
Freely selectable
Recorder digital channels
0…32 channels
Freely selectable analogue and binary signals
5ms sample rate (FFT)
Performance
Sample rate
8, 16, 32 or 64 sample / cycle
Recording length
0.1…1800, setting step 0.001
Maximum length according chosen signals
Amount of recordings
0…100, 60MB shared flash memory reserved
Maximum amount of recordings according chosen signals and operation time setting
combined
9.2.3.4. Circuit breaker wear monitor (CBW)
Table. 9.2.3.4. - 289. Circuit breaker wear monitor (CBW) technical data
Pick-up
Breaker characteristics settings:
-Nominal breaking current
-Maximum breaking current
-Operations with nominal current
-Operations with maximum breaking current
0.00…100.00 kA by step of 0.001 kA
0.00…100.00 kA by step of 0.001 kA
0…200000 Operations by step of 1 Operation
0…200000 Operations by step of 1 Operation
Pick-up setting for Alarm 1 and Alarm 2
0…200000 operations, setting step 1 operation
Inaccuracy
Inaccuracy for current/operations counter
- Current measurement element
- Operation counter
0.1xIn > I < 2 xIn ±0.2% of measured current, rest 0.5%
±0.5% of operations deducted
9.2.3.5. Total harmonic distortion (THD)
Table. 9.2.3.5. - 290. Total harmonic distortion (THD) technical data
Input signals
Input magnitudes
Current measurement channels FFT result up to 31.st harmonic
component.