Figure. 5.2.1. - 8. Example connection (S1 always to odd connector regardless the CT direction). CT direction is selected under
differential function
Please see the above gure, as a result of the direction of the CTs and according to the fact that P1/S1
side of the CTs are always wired to the odd inputs of the relay CT module, the “Differential calculation
mode” under the
Protection
→
TrafoModule
→
Idx> [87T,87N]
→
Settings
has to be set as “Add”. The
difference to the rst application is that here the CTs are pointing towards the protected object instead
of pointing through it.
Initial data of the connection and the ratings are presented in following table.
Table. 5.2.1. - 5. Initial data from example connection.
Machine nominal power: 153MVA
Machine high voltage side nominal amplitude: 132kV
Machine low voltage side nominal amplitude: 15kV
AQ-T257
Instruction manual
Version: 2.00
© Arcteq Relays Ltd
18