![Arcteq AQ-T257 Скачать руководство пользователя страница 163](http://html1.mh-extra.com/html/arcteq/aq-t257/aq-t257_instruction-manual_2964955163.webp)
Figure. 5.4.18. - 82. When everything is set up correctly in the relay and when the transformer is feeding the load with nominal
power the result should look like this with the example settings and transformer.
Four characteristics here present the setting variations based into “Average” and “Maximum” restraint
calculation modes. (Figures A, B with average mode and C, D max mode).
Basically in between these presented restraint calculation modes the characteristics are now set to
equally sensitive.
Also the variations of Turnpoint1 setting either to 0.01xIn or 1.0xIn are presented (Figures A, C with
Turnpoint 1 set to 1.00 xIn and B, D with Turnpoint 1 set to 0.01 xIn).
AQ-T257
Instruction manual
Version: 2.00
© Arcteq Relays Ltd
162