Sync timeout
0.000…
1800.000s
0.02s 0.2s
Setting for synchrocheck wait timeout. If the synchrocheck permission is
not received during this set time the close command will be rejected with
error message. (visible only if Use Synchrocheck is “Yes”)
Use Object
ready
Ready High
Ready Low
Not in use
-
Not in
use
Selection if object ready condition is in use for circuit breaker close
command. Selection can be either “1” or “0” for object ready or not in
use.
Breaker
traverse time
0.02…
500.00s
0.02s 0.2s
Maximum time between open and close status when breaker switches. If
this time is exceeded and both open and closed status inputs are active
status Bad is activated. If neither of the status inputs are active after the
delay Intermediate status is activated.
Sync wait
timeout
0.02…
500.00s
0.02s 0.2s
If synchronization ok is not received during this set time the close
command will be rejected with error message. (visible only if Use
synchrocheck is set to “In use”)
Obj Ready
wait timeout
0.000…
500.00s
0.02s 0.2s
If the object ready is not received during this set time the close command
will be rejected with error message. (visible only if Use Object is either
“High” or “Low”)
Max Close
pulse length
0.000…
500.00s
0.02s 0.2s
Maximum length for close pulse from the output relay to the controlled
object. If the object operates faster than this set time the control pulse will
be reset status change is detected.
Max Open
pulse length
0.000…
500.00s
0.02s 0.2s
Maximum length for open pulse from the output relay to the controlled
object. If the object operates faster than this set time the control pulse will
be reset status change is detected.
Control
termination
timeout
0.000…
500.00s
0.02s 10s
Control pulse termination timeout. If the object has not changed it status
in this given time the function will issue error event and the control is
ended. This parameter is common for both open and close commands.
Final Trip
pulse length
0.000…
500.00s
0.02s 0.2s
When nal trip is executed by the object ObjectX Final Trip signal
activates. If this parameter is set to 0s the signal is continuous. This can
be used in the matrix or the logic editor.
The pick-up activation of the function is not directly equal to start-signal generation of the function.
Start signal is allowed if blocking condition is not active.
Blocking and interlocking
For each controllable object can be set interlocking and blocking conditions for open and close
separately. Blocking and interlocking can be based on other object statuses, software function or
binary input. For example, interlocking can be set for object close based on earthing disconnector
position.