9.2.1.16. Active/Reactive/Apparent power protection (32/37) PQS>/<
Table. 9.2.1.16. - 277. Power (32/37) PQS>/< technical data
Input signals
Input magnitudes
Phase current and voltage fundamental freq RMS
Magnitude selection
P, Q or S value based on chosen/set nominal amplitude
Comparator selection
> or <
Pick-up
> or <
-500.000...500.000 %/MVAn, setting step 0.005 %/MVAn
Inaccuracy
-Active/Reactive/Apparent power
Typically <1.0 %P
SET
Operation time
De nite time function operating time setting
0.00…1800.00 s, setting step 0.005 s
Inaccuracy
-De nite Time (Pm/Pset ratio 1.05
→
)
±1.0 % or ±35 ms
Instant operation time
Start time and instant operation time (trip):
(PQSm/PQSset ratio 1.05
→
)
<40 ms
Reset
Reset ratio
0.97/1.03 x Pset
Instant reset time and start-up reset
<40 ms
Note!
Voltage measurement starts from 0.5V and current measurement from 25mA. In case either or
both is missing the measured magnitude is forced to 0MW/MVar/MVA. Avoid using setting that
should operate below relay current squelch limit (25mA on relay terminal).
9.2.1.17. Resistance temperature detector alarm (49RTD) T>
Table. 9.2.1.17. - 278. Resistance temperature detector alarm (49RTD) technical data
Inputs
Input magnitudes
Measured temperatures
Alarm channels
12 individual alarm channels
Settable alarms
Two per each channel total of 24 alarms available
Pick-up
Alarm setting range
Inaccuracy
Reset ratio
101.00…2000.00 deg, setting step 0.1 deg either under or over setting.
±3% of set pick-up value
97% of the pick-up setting
Operation
Operating time
Typically <500 ms
9.2.1.18. Transformer monitoring function (TRF)
Table. 9.2.1.18. - 279. Transformer monitoring function (TRF) technical data