Figure. 5.5.1. - 114. Instant low command utilized in addition to two time delayed windows.
Pick up setting recommendation for the instant low function is maximum allowed overvoltage
subtracted with tap effect. By this way there should not be situation where the voltage is allowed pass
longer time over the maximum allowed voltage. For example if the maximum allowed overvoltage is
10% by local standards and tap effect for the transformer is 1.67% instant low function pick-up should
be set 10% - 1.67% = 8.33%.