Figure. 5.4.10. - 52. Selectable measurement magnitudes with 3LL+U4 VT connection. If no residual voltage is connected,
phase-to-earth voltages are not available.
Figure. 5.4.10. - 53. Selectable measurement magnitudes with 2LL+U4 VT connection. If no residual voltage is connected
phase-to-earth voltages are not available.
P-P Voltages and P-E Voltages selections follow phase-to-neutral or phase-to-phase voltages in the
rst three voltage channels (or two rst voltage channels in 2LL+U3+U4 mode). U4 selection follows
voltage in channel 4. U3Input selection follows only the voltage in channel 3 if 2LL+U3+U4 mode is in
use.
Pick-up characteristics
Pick-up of the UV function is controlled by Uset setting parameter, which de nes the minimum allowed
measured voltage before action from the function. The function constantly calculates the ratio in
between of the Uset and measured magnitude (Um) per all three voltages. Reset ratio of 103 % is
inbuilt in the function and is always related to the Uset value. The setting value is common for all
measured amplitudes and single-, dual- or each voltage Um decrease below the Uset value will cause
pick-up operation of the function.
Table. 5.4.10. - 107. Pick-up characteristics setting
Name
Description
Range
Step
Default
Uset
Pick-up setting
0.00 …
120.00%Un
0.01%Un 60%Un
AQ-T257
Instruction manual