Rated auxiliary voltage
Pick-up threshold
Release threshold
24Vdc
≥
16Vdc
≤
15Vdc
Scanning rate
5 ms
Polarity
Normally Off
Current drain
3 mA
Terminal block connection
Solid or stranded wire
Phoenix Contact MSTB2,5-5,08
Maximum wire diameter:
2.5mm
2
NOTE! Polarity has to be correct.
9.1.3.4. mAout & mAin module
Table. 9.1.3.4. - 257. mA output & mA input module technical data
Signals
Output magnitudes
Input magnitudes
4 x mA output signal (DC)
1 x mA input signal (DC)
mA input
Range (hardware)
Range (measurement)
Inaccuracy
0...33 mA
0...24 mA
±0.1 mA
Update cycle
Response time @ 5ms cycle
Update cycle time inaccuracy
5...10000 ms, setting step 5ms
~ 15 ms (13...18ms)
max. +20 ms above set cycle
mA input scaling range
Output scaling range
0...4000 mA
-1000000...1000000, setting step 0.0001
mA output
Inaccuracy @ 0...24 mA
±0.01 mA
Response time @ 5ms cycle [Fixed]
< 5 ms
mA output scaling range
Source signal scaling range
0...24 mA, setting step 0.001mA
-1000000...1000000, setting step 0.0001
9.1.3.5. RTD & mA input module
Table. 9.1.3.5. - 258. RTD & mA input module technical data
Channels 1-8
2/3/4-wire RTD and thermocouple sensors
Pt100 or Pt1000
Type K, Type J, Type T and Type S
Channels 7 & 8 support mA measurement
Measurement range
mA input range
0-33mA
AQ-T257
Instruction manual
Version: 2.00
333
© Arcteq Relays Ltd