![Arcteq AQ-T257 Скачать руководство пользователя страница 324](http://html1.mh-extra.com/html/arcteq/aq-t257/aq-t257_instruction-manual_2964955324.webp)
8.11. mAout & mAinput module (option)
Figure. 8.11. - 188. mA output & input module connections.
Connector
Description
SlotX 1
connector (0-24mA)
SlotX 2
mAout1 – connector (0-24mA)
SlotX 3
connector (0-24mA)
SlotX 4
mAout2 – connector (0-24mA)
SlotX 5
connector (0-24mA)
SlotX 6
mAout3 – connector (0-24mA)
SlotX 7
connector (0-24mA)
SlotX 8
mAout4 – connector (0-24mA)
SlotX 9
mAin1 + connector (0-33mA)
SlotX 10
mAin1 – connector (0-33mA)
mA output module is an add-on module with four (4) mA outputs and one (1) mA inputs. mA option
card includes 4 pcs mA-outputs that are grouped in 2 galvanically isolated groups. The option card
also has one galvanically isolated mA-input channel.
This module can be ordered directly as factory installed option or it can be eld upgraded if needed
after the rst installation of the IED.
The mA Outputs are user settable in the mA Outputs control function.
8.12. Installation dimensioning
IED can be installed either to a standard 19” rack or cut-out to a switchgear panel (Installation type of
the device has to be de ned by ordering option). When installing to a rack, the device will take ½ of the
rack width and total of two devices can be installed to same rack in parallel. Device panel installation
and cut-outs are described below.
AQ-T257
Instruction manual
Version: 2.00
323
© Arcteq Relays Ltd