Figure. 5.4.19. - 95. Frequency reference channels.
An example, 500A of current measured on primary side, while xed frequency is set to 50Hz: In case
the frequency would drop to 46Hz, the actual current measurement would be 460A. An error of 40A
would be measured in the system.
Events
The VMEM function generates events from the status changes of various activities. To main event
buffer is possible to select status “On” or “Off” messages.
Table. 5.4.19. - 161. Event codes of the VMEM function.
Event Number
Event channel
Event block name
Event Code
Description
12160
190
M1VT1
0
Voltage memory enabled
12161
190
M1VT1
1
Voltage memory disabled
12162
190
M1VT1
2
Voltage low detected On
12163
190
M1VT1
3
Voltage low detected Off
12164
190
M1VT1
4
Current high detected On
12165
190
M1VT1
5
Current high detected Off
12166
190
M1VT1
6
Frequency tracked from CT On
12167
190
M1VT1
7
Frequency tracked from CT Off
12168
190
M1VT1
8
Using Voltage memory On
12169
190
M1VT1
9
Using Voltage memory Off
12170
190
M1VT1
10
Voltage memory blocked On
12171
190
M1VT1
11
Voltage memory blocked Off
5.4.20. Resistance temperature detectors (Modbus IO) (RTD) (49T)
Resistance Temperature Detectors (RTD) can be used to measure temperatures from the motor as well
as ambient temperature. Typically RTD is PT100 type or thermocouple. External Modbus based RTD
modules are supported up to three separate modules which each can hold up to eight measurement
elements. For the alarm function (RTD / 49T) can be set 12 individual element monitors which each
can be set to alarm two separate alarms from the selected input. Alarms and measurements can be
set in either degrees Centigrade or Fahrenheit.
The principal structure of RTD alarm function is shown in following gure.
To set the RTD measurement rst the measurement module needs to be set to scan the wanted RTD
elements. Currently Modbus based modules are supported. For the communication rst needs to be
set bitrate, databits, parity, stopbits and ModbusIO protocol. These are set at
Communication
→
Connections
.
After the communication is set the wanted channels are selected from the ModbusIO tab under
Communication
→
Protocols
. There are three separate modules available for selection.
AQ-T257
Instruction manual
Version: 2.00