LV side Star
or Zigzag /
Delta
0:Star/Zigzag
1:Delta
-
0:Star/Zigzag TRF,
DIFF
Selection of the LV side connection, star or zigzag or
delta. Selection is visible only if vector group is set to
“0:Manual set”
LV side
grounded
0:Not grounded
1:Grounded
-
0:Not
grounded
TRF,
DIFF
Selection whether the zero sequence compensation
should be applied into LV side currents calculation.
Selection is visible only if vector group is set to
“0:Manual set”
LV side lead
or lag HV
0:Lead
1:Lag
-
0:Lead
TRF,
DIFF
Selection for LV side leads or lags LV side. Selection is
visible only if vector group is set to “0:Manual set”
HV-LV side
phase angle
0.0...360.00deg 0.1deg
0.0deg
TRF,
DIFF
Angle correction factor for HV LV sides, looked from
HV side. e.g. if transformer is Dy1 then set here 30
degrees. Selection is visible only if vector group is set
to “0:Manual set”
HV-LV side
mag
correction
0.0…100.0xIn
0.1xIn
0.0xIn
TRF,
DIFF
Magnitude correction for HV-LV side currents per
unitizing if the currents are not directly matched via
calculation of the nominal values. Selection is visible
only if vector group is set to “0:Manual set”
Check online
HV-LV
con guration
0:-
1:Check
-
0:-
TRF,
DIFF
Check online on energized trafo the con guration
success. (Trafo needs to have current flowing on both
sides as well as there should not be faults seen in order
this to work). Selection is visible only if vector group is
set to “0:Manual set”
Table. 5.4.16. - 138. Calculations of the TRF function.
Name
Range
Step
Default Funcs.
Description
HV side nominal
current(pri)
0.01...50000.00A
0.01A
0.00A
Info
Calculated transformer HV side primary
current.
HV side nominal
current(sec)
0.01…250.00A
0.01A
0.00A
Info
Calculated transformer HV side secondary
current.
HV CT nom to TR nom
factor
0.01…250.00p.u.
0.01p.u.
0.00A
Info
Calculated transformer HV side nominal to
CT primary rate.
LV side nominal
current(pri)
0.01…50000.00A
0.01A
0.00A
Info
Calculated transformer LV side primary
current.
LV side nominal
current(sec)
0.01…250.00A
0.01A
0.00A
Info
Calculated transformer LV side secondary
current.
LV CT nom to TR nom
factor
0.01…250.00p.u.
0.01p.u.
0.00p.u.
Info
Calculated transformer LV side nominal to CT
primary rate.
Transformer nom
impedance
0.01…250.00ohm
0.01ohm 0.00ohm Info
Calculated transformer nominal impedance.
Transformer nom Zk
ohm
0.01…250.00ohm
0.01ohm 0.00ohm Info
Calculated transformer nominal short circuit
impedance.
Transformer nom SC
inductance
0.001…
250.000uH
0.01uH
0.000uH Info
Calculated transformer nominal short circuit
inductance.
Transformer ratio
0.01…250.00
0.01
0.00
Info
Calculated transformer ratio. (HV/LV)
LV side max 3ph SC
curr
0.001…
500.000kA
0.001kA
0.000kA
Info
Calculated maximum three phase short
circuit current in the LV poles of the trafo.
LV side 3ph SC to HV
side
0.001…
500.000kA
0.001kA
0.000kA
Info
Calculated max three phase short circuit
current in LV side shows to HV side.
LV side max 2ph SC
curr
0.001…
500.000kA
0.001kA
0.000kA
Info
Calculated maximum two phase short circuit
current in the LV poles of the trafo.
LV side 2ph SC to HV
side
0.001...500.000kA 0.001kA
0.000kA
Info
Calculated max two phase short circuit
current in LV side shows to HV side.
Table. 5.4.16. - 139. Output signals of the TRF function
Name
Range Step Default
Description
AQ-T257
Instruction manual