Transf.
Vect. group
0:Manual
1:Yy0
2:Yyn0
3:YNy0
4:YNyn0
5:Yy6
6:Yyn6
7:YNy6
8:YNyn6
9:Yd1
10:YNd1
11:Yd7
12:YNd7
13:Yd11
14:YNd11
15:Yd5
16:YNd5
17:Dy1
18:Dyn1
19:Dy7
20:Dyn7
21:Dy11
22:Dyn11
23:Dy5
24:Dyn5
25:Dd0
26:Dd6
-
1:Yy0
TRF,
DIFF
Selection of the transformer vector group. Selection
values from 1 to 26 are prede ned so that just by
selecting correct vector group the scaling and vector
matching is applied in the relay automatically.
In the prede nitions it is assumed that the HV side is
connected to CT1 module and LV side is in CT2 module.
If the protected transformer vector group is not found in
the prede ned list, manual set can be applied by
selecting 0: Manual set.
HV side
Star or
Zigzag /
Delta
0:Star/Zigzag
1:Delta
-
0:Star/Zigzag TRF,
DIFF
Selection of the HV side connection, star or zigzag or
delta. Selection is visible only if vector group is set to
“0:Manual set”
Table. 5.4.18. - 153. Settings related to DIF function pre calculation. (continued).
Name
Range
Step
Default
Funcs.
Description
HV side
grounded
0:Not grounded
1:Grounded
-
0:Not
grounded
TRF,
DIFF
Selection whether the zero sequence compensation
should be applied into HV side currents calculation.
Selection is visible only if vector group is set to
“0:Manual set”
HV side lead
or lag LV
0:Lead
1:Lag
-
0:Lead
TRF,
DIFF
Selection for HV side leads or lags LV side. Selection
is visible only if vector group is set to “0:Manual set”
LV side Star
or Zigzag /
Delta
0:Star/Zigzag
1:Delta
-
0:Star/Zigzag TRF,
DIFF
Selection of the LV side connection, star or zigzag or
delta. Selection is visible only if vector group is set to
“0:Manual set”
LV side
grounded
0:Not grounded
1:Grounded
-
0:Not
grounded
TRF,
DIFF
Selection whether the zero sequence compensation
should be applied into LV side currents calculation.
Selection is visible only if vector group is set to
“0:Manual set”
LV side lead
or lag HV
0:Lead
1:Lag
-
0:Lead
TRF,
DIFF
Selection for LV side leads or lags LV side. Selection is
visible only if vector group is set to “0:Manual set”
HV-LV side
phase angle
0.0...360.00deg 0.1deg 0.0deg
TRF,
DIFF
Angle correction factor for HV LV sides, looked from
HV side. e.g. if transformer is Dy1 then set here 30
degrees. Selection is visible only if vector group is set
to “0:Manual set”
HV-LV side
mag
correction
0.0…100.0xIn
0.1xIn
0.0xIn
TRF,
DIFF
Magnitude correction for HV-LV side currents per
unitizing if the currents are not directly matched via
calculation of the nominal values. Selection is visible
only if vector group is set to “0:Manual set”
Check online
HV-LV
con guration
0:-
1:Check
-
0:-
TRF,
DIFF
Check online on energized trafo the con guration
success. (Trafo needs to have current flowing on both
sides as well as there should not be faults seen in
order this to work). Selection is visible only if vector
group is set to “0:Manual set”
Enable I0d>
(REF) HV
side
0:Disabled
1:Enabled
-
0: Disabled
TRF,DIFF HV side restricted earth fault stage enable/disable
selection.
AQ-T257
Instruction manual
Version: 2.00
175
© Arcteq Relays Ltd