Enable
Alarm 2
0: Disabled
1: Enabled
-
Enabled Enable / Disable selection of the Alarm 2 stage
Alarm 2
Set
0 … 200000
operations
1
operation 100 op
Pick-up threshold for remaining operations. When the remaining
operations is below this setting Alarm 2 signal is activated.
Setting example
Setting example: Tavrida ISM/TEL-24-16 / 800 – 057 circuit breaker
Set the CBW stage as follows:
Parameter
Value
Current 1 (Inom)
0.80 kA
AQ-T257
Instruction manual
Version: 2.00
281
© Arcteq Relays Ltd