![Arcteq AQ-T257 Скачать руководство пользователя страница 233](http://html1.mh-extra.com/html/arcteq/aq-t257/aq-t257_instruction-manual_2964955233.webp)
Setting
group4
0:Not
active
1:Active
-
0:Not
active
Setting group 4 selection, fourth highest priority input for setting group control. Can be
controlled with pulse or steady state signals. If steady state signal is applied no lower
priority than SG1,SG2 and SG3 requests shall be processed.
Setting
group5
0:Not
active
1:Active
-
0:Not
active
Setting group 6 selection, fourth lowest priority input for setting group control. Can be
controlled with pulse or steady state signals. If steady state signal is applied SG6, SG7
and SG8 requests shall not be processed.
Setting
group6
0:Not
active
1:Active
-
0:Not
active
Setting group 6 selection, third lowest priority input for setting group control. Can be
controlled with pulse or steady state signals. If steady state signal is applied SG7 and
SG8 requests shall not be processed.
Setting
group7
0:Not
active
1:Active
-
0:Not
active
Setting group 7 selection, second lowest priority input for setting group control. Can be
controlled with pulse or steady state signals. If steady state signal is applied only SG8
requests shall not be processed.
Setting
group8
0:Not
active
1:Active
-
0:Not
active
Setting group 8 selection, lowest priority input for setting group control. Can be
controlled with pulse or steady state signals. If steady state signal is applied all other
SG requests shall be processed no matter of this signal status.
Active
SG
0…7
1
0
Active SG at the moment. This output signal is used by all other functions.
Events
SG selection function block generates events from its controlling status and applied input signals as
well as unsuccessful control changes and enabled setting groups. For this function is no register
available.
Table. 5.5.2. - 185. Event codes of SGS function.
Event Number
Event channel
Event block name
Event Code
Description
4160
65
SGS
0
SG2 Enabled
4161
65
SGS
1
SG2 Disabled
4162
65
SGS
2
SG3 Enabled
4163
65
SGS
3
SG3 Disabled
4164
65
SGS
4
SG4 Enabled
4165
65
SGS
5
SG4 Disabled
4166
65
SGS
6
SG5 Enabled
4167
65
SGS
7
SG5 Disabled
4168
65
SGS
8
SG6 Enabled
4169
65
SGS
9
SG6 Disabled
4170
65
SGS
10
SG7 Enabled
4171
65
SGS
11
SG7 Disabled
4172
65
SGS
12
SG8 Enabled
4173
65
SGS
13
SG8 Disabled
4174
65
SGS
14
SG1 Request On
4175
65
SGS
15
SG1 Request Off
4176
65
SGS
16
SG2 Request On
4177
65
SGS
17
SG2 Request Off
4178
65
SGS
18
SG3 Request On
4179
65
SGS
19
SG3 Request Off
4180
65
SGS
20
SG4 Request On
4181
65
SGS
21
SG4 Request Off
AQ-T257
Instruction manual
Version: 2.00
© Arcteq Relays Ltd
232