RTD meas 1…16
RTD measurement channels 1…16
Ext RTD meas 1…8
External RTD measurement channels 1…8 (ADAM module)
Parameters
Table. 6.3. - 236. Parameters of Realtime signals to comm
Name
Range
Step
Description
Measurement value recorder
mode
0:Disabled
1:Activated
-
Activation of the function
Scale current values to primary
0:No
1:Yes
-
Selection between using secondary values or primary
values
Slot 1…8 Magnitude selection
0:Currents;
1:Voltages;
2:Powers;
3:Imp.(ZRX).Adm.
(YGB);
4:Others;
-
Selection of slots measured magnitude category
Slot 1…8 Magnitude (x)
Described in table
above
-
Selection of the magnitude in the previously selected
category
AQ-T257
Instruction manual
Version: 2.00
299
© Arcteq Relays Ltd