Figure. 5.4.8. - 41. Differential characteristics for REF function with default settings.
Equations for the differential characteristics are as below:
Differential current (calculation is based on user selected inputs and direction):
Bias current (calculation is based on user selected mode):
Characteristics settings are calculated as follows:
Function blocking
In the blocking element the blocking signal is checked in the beginning of each program cycle.
Blocking signal is received from the blocking matrix for the function dedicated input. If the blocking
signal is not activated when the pick-up element activates, a Trip signal is generated and the function
proceeds to the time characteristics calculation.