Figure. 5.5.1. - 105. Example settings when Scaled curve is used
Tap position with external mA input
Alternative for using RTD&mA card is to use external mA unit ADAM-4016 unit which connects to RS-
485 port.
Tap position with BCD coded binary inputs
Sometimes tap position indication is done by using multiple binary inputs. With BCD coded binary
inputs any one decimal numeral can be represented by a ve-bit pattern. To use BCD coded inputs
set the binary inputs used set
Tap position indication
at the function
Info
page to
BCD coded
inputs
. Binary inputs are then de ned in voltage regulator menu
IO
→
Input signal control
. It is possible
to set up to ve binary inputs for BCD coding. Up to 31 positions can be indicated by using BCD
coding.
AQ-T257
Instruction manual
Version: 2.00
211
© Arcteq Relays Ltd