fset<
fset<<
fset<<<
fset<<<<
Pick-up setting
5.00…75.00Hz
0.01Hz
49Hz
The pick-up activation of the function is not directly equal to start-signal generation of the function.
Start signal is allowed if blocking condition is not active.
Operating time characteristics for trip and reset
This function supports de nite time delay (DT). For detailed information on this delay type refer to
chapter General properties of a protection function.
Function blocking
In the blocking element the block signal is checked at the beginning of each program cycle. Blocking
signal is received from the blocking matrix for the function dedicated input. If the blocking signal is not
activated when the pick-up element activates, a START signal is generated and the function proceeds
to the time characteristics calculation.
If blocking signal is active when pick-up element activates a BLOCKED signal will be generated and the
function shall not process the situation further. If START function has been activated before blocking
signal it will reset and the release time characteristics are processed as in case of when pick-up signal
is reset.
From blocking of the function a HMI display event as well as time stamped blocking event with
information of the startup voltage values and fault type is issued.
Blocking signal can be tested also in the commissioning phase of the stage by software switch signal
when relay common and global testing mode is activated.
User settable variables are binary signals from the system. Blocking signal needs to reach the IED
minimum of 5 ms before the set operating delay has passedfor blocking to be active in time.
Events
The FRQV function generates events and registers from the status changes of start, trip and blocked.
To main event buffer it’s possible to select status “On” or “Off” messages.
In the function is available 12 last registers where the triggering event of the function (start, trip or
blocked) is recorded with time stamp and process data values.
Table. 5.4.13. - 127. Event codes of FRQV function.
Event Number
Event channel
Event block name
Event Code
Description
6336
99
FRQV1
0
f> Start ON
6337
99
FRQV1
1
f> Start OFF
6338
99
FRQV1
2
f> Trip ON
6339
99
FRQV1
3
f> Trip OFF
6340
99
FRQV1
4
f>> Start ON
6341
99
FRQV1
5
f>> Start OFF
6342
99
FRQV1
6
f>> Trip ON
6343
99
FRQV1
7
f>> Trip OFF
6344
99
FRQV1
8
f>>> Start ON
6345
99
FRQV1
9
f>>> Start OFF
AQ-T257
Instruction manual
Version: 2.00
© Arcteq Relays Ltd
122