Table. 5.4.6. - 84. Event codes of the HOC function instances.
Event Number
Event channel
Event block name
Event Code
Description
2368
37
HOC1
0
Start ON
2369
37
HOC1
1
Start OFF
2370
37
HOC1
2
Trip ON
2371
37
HOC1
3
Trip OFF
2372
37
HOC1
4
Block ON
2373
37
HOC1
5
Block OFF
2432
38
HOC2
0
Start ON
2433
38
HOC2
1
Start OFF
2434
38
HOC2
2
Trip ON
2435
38
HOC2
3
Trip OFF
2436
38
HOC2
4
Block ON
2437
38
HOC2
5
Block OFF
2496
39
HOC3
0
Start ON
2497
39
HOC3
1
Start OFF
2498
39
HOC3
2
Trip ON
2499
39
HOC3
3
Trip OFF
2500
39
HOC3
4
Block ON
2501
39
HOC3
5
Block OFF
2560
40
HOC4
0
Start ON
2561
40
HOC4
1
Start OFF
2562
40
HOC4
2
Trip ON
2563
40
HOC4
3
Trip OFF
2564
40
HOC4
4
Block ON
2565
40
HOC4
5
Block OFF
In the register of the HOC function is recorded start, trip or blocked “On” event process data. In the
table below is presented the structure of HOC function register content. This information is available in
12 last recorded events for all provided instances separately.
Table. 5.4.6. - 85. Register content
Date & Time
Event
code
Fault type
Trigger
current
Fault
current
Prefault
current
Trip time
remaining
Used
SG
dd.mm.yyyy
hh:mm:ss.mss
2368-2565
Descr.
L1-G …
L1-L2-L3
Start average
current
Trip -20 ms
averages
Start -200 ms
averages
0ms -1800s
1 - 8
5.4.7. Circuit breaker failure protection CBFP (50BF)
Circuit breaker failure protection (CBFP) function is used for monitoring the circuit breaker operation
after it has been tripped. CBFP function can be used for Retrip to the failing breaker and if the Retrip
fails the upstream breaker can be tripped by using CBFP output. Retrip functionality can be disabled if
the breaker does not have two open coils.