background image

 ASTRO-30       2 Relay Output  (8A)      

  24 programs

Astronomical and/or time switching function

Automatic or manual summer/winter time option

ON/OFF switching times

Automatic sunrise/sunset calculation using coordinates 
and time

Quiet mode

PIN code protection

 2 Manual modes

Astronomical 
Time Relay

ASTRO-30 / ASTRO-31

Push in this direction and
 remove the battery cover

General:

ASTRO is a digital time switch that calculates the sunset and sunrise 
times by using coordinates and real time clock. It operates according to 
the program setting and it has no need for a photocell sensor. Device 
could be used as astronomical or digital time switch.
ASTRO has two reserves to protect the real time clock and calender 
against power outage. 
For long term reserve there is CR2032 battery. If the device is powered, 
battery life is approx. 5 years. When the battery life is expired,the user is 
able to replace the battery easily.
Super capacitor is used for short time power failures. It supplies the 
device for 3-7 hours. In this case battery is not used, so battery level is 
conserved. 
 

NOTE1:

 Before commissioning the device, please insert the battery into 

the battery compartment .

NOTE2:

 If the device is not powered, ASTRO automatically enters power 

save mode to conserve the battery life. When the device is in this mode 
LCD screen is turned off. The screen would turn on when pressing any  
button and so the user would be able to change the settings and 
programming the device manually. After 15 seconds of inactivity, the 
screen would be turned off again. 

NOTE3: 

4 preset programs are available on the device.
Program 1 : Relay A      Astro        Sunset           ON
Program 2 : Relay A      Astro        Sunrise          OFF
Program 3 : Relay B     Astro         Sunset           ON
Program 4 : Relay B     Time          00:00             OFF

User replaceable battery

Astronomical mode

Timer mode

Monday

Tuesday
Wednesday

Thursday

Friday

Saturday
Sunday

Clock

Date

Relay A

Lock function

Quiet mode

Manual mode

Relay B

Lock function

Quiet mode

Manual mode

12

1

2

3

4

5

6

11

10

9

8

7

Clock faces represent output states of the relay 
contacts during current day. 
Before midday, am icon appears. 
After midday, pm icon appears.
There are two clock faces, on the left for Relay A
and on the right for Relay B.

Warnings:

- The connection of device must be done by authorized technical 
service staff according to the wiring diagram.
 - Before making the connections to device's terminals, please be 
sure that there is no voltage across the cables or terminals. Also be 
sure that the panel is de-energized.
- Before cleaning the device, please be sure that it is de-energized 
and use only dry tissue-paper to clean it. Water or any other 
chemicals used for cleaning may harm the device
- Before commissioning the device, please be sure that the terminal 
connections are made exactly 
the same as in the connection diagram
- To protect the device, please mount it on DIN rail in a panel. 
- Contact your authorized dealer, if a problem occurs with your 
device.
Following the precautions is to prevent the users from physically and 
spiritual damage. The manufacturer is not responsible for any injuries 
or damages due to violation of the warnings. 

Screen Descriptions:

Area of Usage:

- Park, garden and farm irrigation
- Street, park, garden illuminations
- ATM ,store window, billboard 
illuminations

Insert the battery with 
the po) side facing up
as shown in the figure.

Make sure the battery is seated
correctly in the battery slot. 
Replace the battery cover.

Button Functions:

ASTRO is an easy to use device with 3 buttons.
▼    :  Press to move between menus or decrease the 

   

           related parameter.
▲    :  Press to move between menus or increase the 

   

           related parameter.

SET

 :  Press to go into the menu or save the related 

   

           parameter.

www.kael.com.tr                  1

Offset for adjustable programming of sunrise/sunset
times

 ASTRO-31       2 Relay Output  (16A)    

Easy to use with English menu

Real time clock and calender

▲: 

Press two buttons at the same time to go back to the pre-menu screen

Press two buttons long at the same time to return to the main screen.  

Содержание ASTRO-30

Страница 1: ...ode Manual mode Relay B Lock function Quiet mode Manual mode 12 1 2 3 4 5 6 11 10 9 8 7 Clock faces represent output states of the relay contacts during current day Before midday am icon appears After midday pm icon appears There are two clock faces on the left for Relay A and on the right for Relay B Warnings The connection of device must be done by authorized technical service staff according to...

Страница 2: ... only way to deactivate this mode is manually Throughout the manual mode for changing Relay A output it is necessary to push and release button To deactivate this mode for Relay A push button until the hand icon disappears Permanent manual mode for Relay B Push and SET buttons at the same time until the hand icon appears on the right of the screen Permanent manual mode is not deactivated automatic...

Страница 3: ...splay EAST east ERR2 PIN code error ERR5 Program overload error EXIT exit HOUR hour LANGUA language LATITU latitude LOCATE locate STRT M start of quiet mode month STRT Y start of quiet mode year SUMMER summer SUNRSE sunrise SUNSET sunset T ZONE time zone TIME time UNUSED unused USED used UTC coordinated universal time W DAY winter beginning day W HOUR winter beginning hour W MIN winter beginning m...

Страница 4: ...sired relay output is selected Required contact position is selected as ON or OFF Monday If YES is selected program operation is enabled for flashing day If NO is selected program is not used for flashing day This process is repeated for each day of the week After making choice for the last day of the week program could be stored with selecting SAVE or could be cancelled with selecting EXIT DELETI...

Страница 5: ...ogram operation time OFFSET is added to sunrise or sunset time OFFSET This parameter is used to adjust the program operation time OFFSET is subtracted from sunrise or sunset time If timer mode is selected hour minute and second values are entered respectively Sunrise or Sunset is set If it is desired OFFSET would be adjusted For related program desired relay output is selected Required contact pos...

Страница 6: ...ed it is stored by pressing SET button Second parameter is beginning week for the summer in chosen month With using buttons week value is set as 1 2 3 4 or last Third parameter is beginning day for the summer With using buttons day is set Fourth parameter is beginning hour for the summer With using buttons hour value is set Fifth parameter is beginning minutes for the summer With using buttons min...

Страница 7: ... or negative offsets from UTC LOCK FUNCTION LOCK menu could be reached by pressing button in ADJUST sub menus This function could be used to prevent unauthorized persons from using the device If this function is enabled just for Relay A manual mode could not be activated for it But it is possible to activate manual mode for Relay B In this case for reaching the menus PIN code is required If this f...

Страница 8: ...tart Date is 20 03 2011 and stop date 25 03 2011 Quiet Mode starts on 20th March at 00 00 00 am and ends on 25th March at 23 59 59 During this time period Relay A would be off To activate Quiet mode just for 1 day start and stop date should be set as same day PIN PIN menu could be reached by pressing button in ADJUST sub menus If the LOCK function is enabled entering the pin code is required befor...

Страница 9: ...n in ADJUST sub menus By restoring an ASTRO to factory defaults following settings are installed Programs 4 preset programs Lock A B Off Quiet A B Off Manual A B Off Season Auto Location Contrast 7 NOTE Reset an ASTRO to factory defaults does not change the pin code and the real time adjust tıme season locate lock quıet pın langua TURKCE ENGLIS back adjust tıme season locate lock quıet pın languad...

Страница 10: ...vice Additional Reserv Time 3 7 hour Screen LCD Language English Turkish Programming with InfraRed No Mounting To connection rail in electrical panel Storage Temperature 10 ºC 70 ºC Ambient Temperature 0 ºC 50 ºC Device Protection Class IP 20 Connector Protection Class IP 00 Dimensions 2 x DIN modules 58mm 32mm 48mm 90mm 36mm 45mm 62mm 35mm 18 16 15 28 26 25 TECHNICAL DATA www kael com tr 9 CONNEC...