background image

WHITE-RODGERS

T

T

1

2

3

4

 

5

6

Printed in U.S.A.

PART NO. 37-2689D

Replaces 37-2689-3

9512

TYPE 829A-845

RELAY

For Use With Low Voltage Thermostats

INSTALLATION INSTRUCTIONS

Operator:  Save these instructions for future use!

WHITE-RODGERS DIVISION
EMERSON ELECTRIC CO.
9797 REAVIS RD., ST. LOUIS, MO.   63123
(314) 577-1300,

FAX (314) 577-1517

9999 HWY. 48, MARKHAM, ONT. L3P 3J3
(905) 475-4653, FAX (905) 475-4625

R

DESCRIPTION

FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE
INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL
INJURY AND/OR PROPERTY DAMAGE.

Type 829A-845 Relay has double-pole, single-throw
switching action.

This relay is especially suitable for use on hot water
heating installations having forced circulation. It permits
the use of a sensitive low voltage room thermostat to
control the operation of both burner and circulator.

It is equally well suited for use on zoned hot water
installations where a circulator and low voltage thermostat
are used for each zone.

ELECTRICAL DATA
Switch Action:
 Double-Pole, Single-Throw, normally open
Input Voltage:  Terminals (1 & 2) 120V.A.C., 60Hz
Room Thermostat:

Set adjustable heat anticipator at 0.3 Amps. For fixed
anticipation thermostats, use 0.25 to 0.35 Amp. heater.

Rating:

Terminals (3 & 4 and 5 & 6)

Total load must not exceed 2000 VA.
Motor: 
120V.A.C.

10F.L.A.

60L.R.A.

240V.A.C.

6F.L.A.

36L.R.A.

Pilot Duty:50VA @ 24 Volts

SPECIFICATIONS

To prevent electrical shock and/or equipment
damage, disconnect electric power to system, at
main fuse or circuit breaker box, until installation
is complete.

If in doubt about whether your wiring is millivolt, line, or
low voltage, have it inspected by a qualified heating and
air conditioning contractor, electrician, or someone famil-
iar with basic electricity and wiring.

Do not exceed the specification ratings.

All wiring must conform to local and national electrical
codes and ordinances.

This control is a precision instrument, and should be
handled carefully. Rough handling or distorting compo-
nents could cause the control to malfunction.

PRECAUTIONS

CAUTION

Do not use on circuits exceeding specified
voltages. Higher voltages will damage control
and could cause shock or fire hazard.

WARNING

PRINCIPLE OF OPERATION

The 829A-845 relay is provided with a self-contained
transformer with a low voltage secondary output for
energizing the relay coil.

Line voltage lines should be connected to the terminals
marked “1 & 2” for power to reach the transformer.

Closing the thermostat circuit energizes the relay coil which
in turn closes the circuits between terminals 3 and 4 and also
between 5 and 6.

Opening the thermostat circuit de-energizes the relay coil,
breaking the circuits between terminals 3 and 4 and also
between 5 and 6.

DOTTED LINES

INDICATE FIELD

WIRING

Fig. 1

RELAY
COIL

N

LINE

HOT

TO LINE AND LOAD

OR PILOT DUTY

TO LINE AND LOAD

OR PILOT DUTY

Содержание 829A-845

Страница 1: ...240V A C 6F L A 36L R A Pilot Duty 50VA 24 Volts SPECIFICATIONS To prevent electrical shock and or equipment damage disconnect electric power to system at mainfuseorcircuitbreakerbox untilinstallation is complete If in doubt about whether your wiring is millivolt line or low voltage have it inspected by a qualified heating and air conditioning contractor electrician or someone famil iar with basic...

Страница 2: ... for heat both the burner and circulator start If excessive boiler temperature causes high limit to open the circulator continues to run but the burner shuts down until the high limit recloses When the thermostat is satisfied both the burner and circulator stop Fig 3a 4a Diagram for Gas Fired System T 1 4 2 3 T 5 6 Fig 2 BURNER MOTOR THERMOSTAT FIELD INSTALLED JUMPERS Fig 3 TRANS HIGH LIMIT 24 VAC...

Страница 3: ...ture year round When the thermostat calls for heat the burner starts The circulator also starts if boiler temperature is above setting of circulator control If excessive boiler temperature causes high limit to open the circulator continues to run but the burner shuts down until the high limit recloses Whenlowboilertemperaturecausesthecirculatorcontrol to open burner stays on but the circulator sto...

Страница 4: ...celui ci par un électricien par un entrepreneur agréé en chauffage et climatisation ou par une personne qui a des connaissances de base en électricité et en câblage Ne dépassez pas les charges nominales Tout le câblage doit être conforme aux codes et règlements locaux et nationaux qui régissent les installations électriques Cette commande est un instrument de précision qui doit être manipulé avec ...

Страница 5: ...de d unrelaisunipolaireunidirectionnel SPST detype809Aau lieu d un relais bipolaire unidirectionnel DPST de type 829A Référez vousauschémadecâblagefourniavecles directivesdurelaisdetype809A NOTE CÂBLAGE Tout le câblage doit être conforme aux codes et règlements locaux et nationaux qui régissent les installations électriques SOUS TENSION RÉSEAU N VERS LA CHARGE VERS L ALIMENTATION THERMOSTAT À BASS...

Страница 6: ...ue de fonctionner mais le circulateur s arrête jusqu à ce que le circuit de la commande du circulateur soit à nouveau fermé Une fois le thermostat satisfait le circulateur s arrête Le brûleur s arrêteaussisilatempératuredelachaudièreestsupérieureau point de consigne du limiteur minimum T 1 4 2 3 T 5 6 ZC ZR B1 B2 C1 C2 1 2 T T VERS LES RELAIS 829A 845 ADDITIONNELS DES AUTRES ZONES CAVALIER Fig 7 M...

Отзывы: