S3PH, P3PH, Q3PH
Three phase apparent, active and reactive power
SL1, SL2, SL3, PL1, PL2, PL3,
QL1, QL2, QL3
Phase apparent, active and reactive powers
tan 3PH, tan L1, tan L2, tan L3
Tan (φ) of three phase powers and phase powers
cos 3PH, cos L1, cos L2, cos L3
Cos (φ) of three phase powers and phase powers
Impedances and admittances
Description
RL12, RL23, RL31
XL12, XL23, XL31,
RL1, RL2, RL3
XL1, XL2, XL3
Z12, Z23, Z31
ZL1, ZL2, ZL3
Phase-to-phase/Phase-to-neutral resistances, reactances and impedances
Z12Ang, Z23Ang, Z31Ang,
ZL1Ang, ZL2Ang, ZL3Ang
Phase-to-phase/Phase-to-neutral impedance angles
Rseq, Xseq, Zseq
RseqAng, XseqAng, ZseqAng
Positive sequence resistance, reactance and impedance values and angles
GL1, GL2, GL3, G0
BL1, BL2, BL3, B0
YL1, YL2, YL3, Y0
Conductances, susceptances and admittances
YL1angle, YL2angle, YL3angle
Y0angle
Admittance angles
Others
Description
System f.
Used tracking frequency at the moment
Ref f1
Reference frequency 1
Ref f2
Reference frequency 1
M thermal T
Motor thermal temperature
F thermal T
Feeder thermal temperature
T thermal T
Transformer thermal temperature
RTD meas 1…16
RTD measurement channels 1…16
Ext RTD meas 1…8
External RTD measurement channels 1…8 (ADAM module)
Reported values
When triggered function will hold the recorded values of the set up 8 channels. In addition to this
tripped stage, overcurrent fault type and voltage fault types are reported to SCADA.
Table. 5.6.7. - 229. Reported values of measurement value recorder
Name
Range
Step
Description
Tripped stage
0:-
1:I> Trip
2:I>> Trip
3:I>>> Trip
4:I>>>> Trip
5:IDir> Trip
6:IDir>> Trip
7:IDir>>> Trip
8:IDir>>>> Trip
9:U> Trip
10:U>> Trip
11:U>>> Trip
12:U>>>> Trip
13:U< Trip
14:U<< Trip
15:U<<< Trip
16:U<<<< Trip
-
Tripped stage
AQ-T257
Instruction manual
Version: 2.00
© Arcteq Relays Ltd