![Arcteq AQ-T257 Скачать руководство пользователя страница 52](http://html1.mh-extra.com/html/arcteq/aq-t257/aq-t257_instruction-manual_2964955052.webp)
1861
29
NEF4
5
Block OFF
In the register of the NEF function is recorded start, trip or blocked “On” event process data. In the
table below is presented the structure of NEF function register content. This information is available in
12 last recorded events for all provided instances separately.
Table. 5.4.2. - 60. Register content
Date & Time
Event
code
Fault
type
Trigger
current
Fault
current
Prefault
current
Trip time
remaining
Used
SG
dd.mm.yyyy
hh:mm:ss.mss
1664-1861
Descr.
A-G-R…
C-G-F
Start average
current
Trip -20 ms
averages
Start -200 ms
averages
0ms -1800s
1 - 8
5.4.3. Directional overcurrent IDir> (67)
Directional overcurrent function (DOC) is used for directional instant- and time delayed
overcurrent/short circuit protection for various applications including feeder and machine applications
of utilities and industry. IED with both voltage and current protection module may have four available
instances of the function (IDir>, IDir>>, IDir>>>, IDir>>>>). Function constantly measures phase
current magnitudes on which the operating decisions are based. Selectable monitored phase current
magnitudes are fundamental component RMS, TRMS values (including harmonics up to 31
st
) or peak-
to-peak values. Blocking signal and setting group selection controls the operating characteristics of the
function during normal operation.
Outputs of the function are Start Trip and Blocked signals. Setting parameters are static inputs for the
function which are changed only by user input in the setup phase of the function. Directional
overcurrent function utilizes total of eight separate setting groups which can be selected from one
common source.
The function can be operating on instant or time delayed mode. In time delayed mode the operation
mode can be switched to de nite time or IDMT mode. For IDMT operation IEC and ANSI standard time
delays are supported as well as custom parameters. Function includes CT saturation checking which
allows the function to start and operate accurately also in case of CT saturation condition.
The operational logic consists of input magnitude and angle processing, input magnitude selection,
saturation check, threshold comparator, block signal check, time delay characteristics and output
processing. The basic design of the protection function is 3-pole operation.
Inputs for the function are the operating mode selections, setting parameters and measured and pre-
processed current magnitudes and binary input signals. Function outputs START, TRIP and BLOCKED
signals which can be used for direct IO controlling and for user logic programming. The function
registers its operation into 12 last time-stamped registers and also generates general time stamped
ON/OFF events to the common event buffer from each of the three output signals. In instant operating
mode the function outputs START and TRIP events simultaneously with equivalent time stamp. Time
stamp resolution is 1ms. Function provides also cumulative counters for START, TRIP and BLOCKED
events.
Simpli ed function block diagram of DOC function is presented in the gure below.
AQ-T257
Instruction manual
Version: 2.00
51
© Arcteq Relays Ltd