![Arcteq AQ-T257 Скачать руководство пользователя страница 108](http://html1.mh-extra.com/html/arcteq/aq-t257/aq-t257_instruction-manual_2964955108.webp)
De nite
operating
time delay
0.000…
1800.000s 0.005s 0.040s
De nite time operating delay. Setting is active and visible when Delay Type is
selected to DT.
When set to 0.000 s the stage operates as instant (PIOC, 50) stage without
added delay. When the parameter is set to 0.005 – 1800 s the stage operates
as independent delayed (PTOC, 51).
Time dial
setting k
0.01…
60.00s
0.01s
0.05s
Setting is active and visible when Delay Type is selected to IDMT.
Time dial / multiplier setting for IDMT characteristics.
IDMT
Multiplier
0.01…
25.00s
0.01s
1.00
Setting is active and visible when Delay Type is selected to IDMT.
IDMT time multiplier in the Um/Uset power.
Table. 5.4.10. - 109. Reset time characteristics setting parameters.
Name
Range
Step
Default
Description
Release Time
delay
0.000…
150.000s 0.005s 0.06s
Resetting time. Time allowed in between of pick-ups if the pick-up has not
lead into trip operation. During this time the start signal is held on for the
timers if delayed pick-up release is active.
Delayed Pick-
up release
No
Yes
-
Yes
Resetting characteristics selection either time delayed or instant after pick-
up element is released. If activated the start signal is reset after set release
time delay.
Time calc
reset after
release time
No
Yes
-
Yes
Operating timer resetting characteristics selection. When active the
operating time counter is reset after set release time if pick-up element is
not activated during this time. When disabled the operating time counter is
reset directly after the pick-up element reset.
Continue time
calculation
during release
time
No
Yes
-
No
Time calculation characteristics selection. If activated the operating time
counter is continuing until set release time even the pick-up element is reset.
Resetting characteristics can be set according to the application. Default setting is delayed with 60 ms
and the time calculation is held during the release time.
When using the release delay option where the operating time counter is calculating the operating time
during the release time, function will not trip if the input signal is not activated again during the release
time counting.
Events and registers
The UV function generates events and registers from the status changes of start, trip and blocked. To
main event buffer is possible to select status “On” or “Off” messages. The UV function offers four
independent instances which events are segregated for each instance operation.
In the function is available 12 last registers where the triggering event of the function (start, trip or
blocked) is recorded with time stamp and process data values.
Table. 5.4.10. - 110. Event codes of UV function instance 1 – 4.
Event Number
Event channel
Event block name
Event Code
Description
5696
89
UV1
0
Start ON
5697
89
UV1
1
Start OFF
5698
89
UV1
2
Trip ON
5699
89
UV1
3
Trip OFF
5700
89
UV1
4
Block ON
5701
89
UV1
5
Block OFF
5702
89
UV1
6
Undervoltage Block On
AQ-T257
Instruction manual
Version: 2.00
107
© Arcteq Relays Ltd