5.6.7. Measurement value recorder
Measurement value recorder function records the value of selected magnitudes at the time of given
trigger signal. An example application for this function is to record fault currents or voltages at the time
of tripping the breaker but it can be used also to record the values from any user set trigger signal.
Value recorder is capable of recording either per unit value or primary value which is user settable.
Optionally it is possible to set the function to record the overcurrent or voltage fault type. The function
operates instantly from trigger signal.
Additionally, the measurement value recorder function has integrated fault display which displays the
current fault values in case of I>, Idir>, I0>, I0dir>, f<, f>, U< or U> trips. When any of these functions
trip fault values and fault type are displayed over the mimic view. The view can be enabled by activating
VREC Trigger On
in menu
Tools
→
Events and logs
→
Set alarm events
. Resetting of the fault values is
done by input selected in General menu.
Measured input values
Function block uses analog current and voltage measurement values. From these values relay
calculates the secondary and primary values of currents, voltages, powers, impedances and other
values.
Up to 8 magnitudes can be set to be recorded when function is triggered. Overcurrent fault type,
voltage fault type and tripped stage can be recorded and reported forward to SCADA.
NOTE: Available measurement values depend on the IED type. If only current analog measurements
are available, it is possible to use only signals which use just current. The same applies if only voltage is
available.
Currents
Description
IL1ff, IL2ff, IL3ff, I01ff, I02ff
Fundamental frequency current measurement values of phase currents and residual
currents
IL1TRMS, IL2TRMS, IL3TRMS,
I01TRMS, I02TRMS
TRMS current measurement values of phase currents and residual currents
IL1,2,3 & I01/I02 2
nd
h., 3
rd
h., 4
th
h., 5
th
h., 7
th
h., 9
th
h., 11
th
h., 13
th
h., 15
th
h., 17
th
h., 19
th
h.
Magnitudes of phase current components: Fundamental, 2
nd
harmonic, 3
rd
harmonic,
4
th
harmonic, 5
th
harmonic 7
th
, harmonic 9
th
, harmonic 11
th
, harmonic 13
th
, harmonic
15
th
, harmonic 17
th
, harmonic 19
th
harmonic current.
I1,I2,I0Z
Positive sequence current, negative sequence current and zero sequence current
I0CalcMag
Residual current calculated from phase currents
IL1Ang, IL2Ang, IL3Ang,
I01Ang, I02Ang, I0CalcAng,
I1Ang, I2Ang
Angles of each measured current
Voltages
Description
UL1Mag, UL2Mag, UL3Mag,
UL12Mag, UL23Mag, UL31Mag
U0Mag, U0CalcMag
Magnitudes of phase voltages, phase-to-phase voltages and residual voltages.
U1 Pos.seq V mag, U2 Neg.seq V
mag
Positive and negative sequence voltages.
UL1Ang, UL2Ang, UL3Ang,
UL12Ang, UL23Ang, UL31Ang
U0Ang, U0CalcAng
Angles of phase voltages, phase-to-phase voltages and residual voltages.
U1 Pos.seq V Ang, U2 Neg.seq V
Ang
Positive and negative sequence angles.
Powers
Description
AQ-T257
Instruction manual
Version: 2.00
287