background image

Code

Type

Sensivity (A)

Tripping delay (s)

Communications

P24642

RGU - 10 MT

0,03-0,1-0,3-0,5-1-3
by direct adjustment
       

5-10-30 by 

SETUP

INS-SEL-0,02-0,1-0,2-0,3-0,4-0,5-0,75-1
              by direct adjustment

3-5-10 by 

SETUP

No Available

P 2 X X X X 0 0 X

Código
 

Code

Código interno
 

Internal code

Tensión de
alimentación

Power supply

230 V a.c. 

110 V a.c.

0

1

RGU-10 MT Electronic earth leakage protection relay with self-reclosing system

For instance, RGU-10 MT supplied by 110 V a.c. 

GENERAL DESCRIPTION

-  Device with programmable differential relay with self-reclosing system. Symbol          in LCD.
-  It has 2 independents outputs by relays. Trip and locked by reclosing.
-  It has 1 input for  external Trip/Reclose. This input is not opto - coupled.
-  Mounting in Rail DIN  46277 (EN 50022) or panel 72x72 by mean accessory (M5ZZF1)
-  Associated to a 

WG

/

WGS 

Series external , toroidal current transformer.

-  It must be asociated to a MCB motorized with or without a trip coil.
-  It verifies connection with differential transformer 

WG/WGS

 by means inductive test.

-  Leakage detection and measurement is via calculating its true efective value (TRMS).
-  Display settings values and instant residual current to its accociated units.

  

DESCRIPTION LED AND BUTTONS.

-  Shows equipment status via a display and 2 LED.
-  5 button  equipment setup and setting.
-  2 button  equipment TEST and RESET.

INDICATION BY LED AND DISPLAY.

-  

TRIP RELAY. 

LED and display signals a change 

   of status by changing from green to red.l 
   Display event type messages or values.

 BETWEN RECLOSURES. 

   

The yellow LED is blinking. Red Display shows the

   tripp cause fluctuating with partial reclosures No

 

LOCKED BY RECLOSURES

.      

   The yellow LED is  fixed. The equipment arrives al
   maximun number of reclosures established by the
   self-reclosing sequence. Red display shows the cause.
-  

No OF RECLOSURES. 

By short press on 

PROG

 the display shows the number of reclosures by

   earth leakage, short ciruit-overload faults and total number. The partial number are floating pages
   In these pages it can configure the self-reclosing sequence by press 

REC 

button.  

RECLOSING THE EQUIPMENT.

-  BY 

TRIP 

LOCKED BY RECLOSURES

   1.  Automathic (earth leakage, short ciruit-overload faults or manual).           Enabled.
   2.  Manual reclose by pushing button 

RESET

   3.  External reclose sytem by remote or communications signal. When it forces a trip by  remote 
   signal, only it can reclose by another remote signal.
   4.  Manual reclose circuit breaker associated.
In the case 2 and 3 the all partial counters of reclosures returns to a zero.

 

RELAY PARAMETERS SETTING 

(

 

t

I

 y std/+ )

d

d

t

d

SETTING TRIP DELAY

The               message   and two   values   appear  on the  screen  after 

  pressing  the

button.  The lowest  value indicates   the current   set value  and the highest  is the 

 t

d    

  values to be configured which are  displayed by pressing

The  selected  value to be  saved  is 

      .  

  displayed by showing the message

 SAVE.

I

I

. . 

d

d

SENSITIVITY SETTING

The same operation as above setting is carried out by pressing 

- SIGNALLING CONTACTS RELAY STATE,  std/+

 . Select the default position of the relay contacts 

  7-8-9 that indicates the situation of locked by reclosures of the device .  In (Std) 8-7 NA  / 8-9 NC 
  and (+) 8-7 NC  / 8-9 NA and  appears the     symbol in display.

- SELF-RECLOSING SYSTEM, REC

.   In   reclosure   partial   numbers   by press  

REC

  button we 

  configure the self-reclosing  sequence  referred  at  the  page which it’s showing us.  By default  is 
  configured  nº10 by  earth leakage protection and nº5 by short-circuit/overload protection.

Tripping cause

Message display

Test
Remote signal trip/reclose
Earth leakage fault
Short circuit / Overload fault

TESt
EXT
DIF / valor
MAG

PROG

+

Others MESSAGES by display

SAVE
EXIT
OVR
ERRt

Enter setting values 
Exits setting mode
Value reading off scale
Poor toroidal conection

M98205801-03-21A

P24642001

  PARAMETERS BY 

DIRECT ADJUSTMENT 

-DELAY SETTING
-

SETUP

 ROTATION

-SENSIVITY SETTING 

-CONTACTS SETTING NO/NC

-ENABLE/DISABLE 
 SELF-RECLOSING SYSTEM 

REC

SREC    No RECLOSURES                TIME SEQUENCES                             RESET TIME

RECLOSE SEQUENCES BY EARTH LEAKAGE CURRENT FAULT 

SREC  No RECLOSURES           TIME SEQUENCE                     RESET TIME

RECLOSE SEQUENCE BY SHORTCIRCUIT/OVERLOAD FAULT

- Tipo 

Relay type: Electronic class A. High frequency current filtering.

- Rated power supply voltage

: 230 o 110 Va.c. (+/- 20%)  50/60 Hz, 6 VA

:

Connections

2

  

0,127 - 2,082 mm

Permissible cable section:          

- Reclosing type: Authomatic, RESET button or by cutting power supply.

:  -10ºC / 50ºC

Operating temperature

  Recommended tightening torque: 0.5-0.6 Nm

             

TECHNICAL FEATURES

  

: 250/230 V a.c.

Rated voltage/Maximum switching voltage

  Maximun Voltage:  275 Va.c.

 13-14-15, 7-8-9 and 5-6

Switch Output contact features

  

: 6/10 A a.c.

Rated current/Maximum instant current

                                                         

  Length of cable to strip:                 7 mm

  

 AC: 2,500 V·A

Rated load in

  Input not using optocoupler

-Characteristics input remote Trip/Reclose 1-2

  Contacts protected by varistor

- Varistor Features

REC

REC

MT

WARNING: The reclosing sequences marked by           are only for motorized circuit breakers with or
without trip coil. I >63 A.  

N

 Capacity:

 Maximun DC Load Breaking

 Maximun opening current

Electrical useful life for AC 
loads: No of cycles

MAG

¡ IMPORTANT !

The relay only self-recloses before a trip by earth leakage, short-circuit/overload current fault. The Test (red button) only
 verifies the relay trips the protection. It recloses only by manual pressing RESET button.

   0                                            DISABLED
   1                      2                   1 minute                                             30 minutes
   2                      2                   1 minute                                             60 minutes
   3                      2                   90 s                                                    30 minutes
   4                      2                   90 s                                                    60 minutes
   

5

                      2                   3 minutes                                            30 minutes

   6                     ...                     ...                                                             ...
   7                     ...                     ...                                                             ...
   8                     ...                     ...                                                             ...

   0                                                                     DISABLED
   1                      6                                 8, 16, 30, 59, 115 and 224 s                   15 minutes
   2                    30                                 20, 40 s and 5 min. to the end                15 minutes
   3                      8                                 30 s, 1, 2, 3, 4, 5, 6 and 7 min                15 minutes
   4                      6                                 10, 20, 30, 60, 130 and 600 s                 15 minutes
   5                      6                                 2, 4 y 8 min. to the end                           15 minutes
   6                      7                                 30 s, 1, 2, 3, 4, 8 and 16 min                  30 minutes
   7                    10                                 1 min                                                       30 minutes
   8                    10                                 90 s                                                         30 minutes
   9                      8                                 2, 4 y 6 minutes to the rest                     15 minutes
 

10

                    10                                 3 minutes                                                30 minutes

 11                      7                                 2, 4, 8, 16, 32, 32 and 32 minutes          15 minutes

 12                    31                                2, 4 and 6 minutes to the rest                  15 minutes
 13                      6                                8 s                                                            15 minutes
 14                     ...                                  ...                                                             ...

MAG

MAG

MAG

MAG

MAG

MAG

MAG

REC

REC

GREEN LED: ON 
RED LED: TRIPPED BY FAULT

 SCREENS /  

SETUP

 

R

RESET button: It reinitiates the operation of the equipment by any event  
                         that tripps it.evento. It indicates the equipment version.

YELLOW LED: Locked by reclosures (fix)
                         Betwen reclosures (blinking)

RST.C

, (

), initiates the partials counters.

NO

TRIP, (

), breaking element

 (without trip coil)

MA

FREQ

, (

) frecuency (Hz)

50

LIM

,(

), range of values (Id / td)

1s, 3A

SEC. T

,  (

),contacts 5-6 [NA/NC]

NO

Default values in 

SETUP

TEST button: It makes a forced firing to verify the protection.

Button

FREQ

LIM

SEC.T

TRIP

Button

   60 Hz

10 s, 30 A

RST.C

   Mb

Pulsador 

PROG

  PsI

   50 Hz

1 s,   3 A

   St

   MA

   YES

   NO

SETUP

 SETTINGS

 A long press in 

 

 activates  the  

SETUP

 settings.  In  this operating 

PROG  

mode by pressing buttons 

 

and      it shows  the submenus and the 

PROG

setting  values  to   modify .  With  

 

these

PROG 

  new  setting  values  are 

validated,  the  message   

SAVE

   is shown  by display  and  exits  setting 

mode. In case of keypad inactive, it  exits setting mode and the message  

EXIT

 is shown by display wihtout changes.

In 

SEC.T

 it defines the working mode of outputs contacts relay 5-6. By 

default 5-6 is normally open (St ) 

In 

TRIP 

(Circuit Breaker), The value      is used when the CB don’t need  a 

trip coil. The value       is used when CB needs  one.

  (LOCKED SIGNAL)

(See graph)

(See graph)

Отзывы: