Functional Description
The cos
ϕ
monitor is used to detect an
underload. Adjustable response value
and response time. It can also be used
together with a frequency converter
(frequency 2 to 200 Hz). Monitoring is
accomplished by recognising the phase
shift between current and voltage. This
phase angle varies according to the load
of the motor. The instrument is
equipped with a green LED for operating
voltage indication and a red LED for
error indication.
Technical Data
Input
nominal voltage
230 V AC
power consumption (max)
1.5 VA
operating voltage range
0.9 - 1.1 x U
N
frequency range
2 ... 200 Hz
duty cycle
100 %
input voltage (motor)
230 V AC / 400 V AC
input current
min. 0.2 A, max. 10 A
(load current)
load inrush current
100 A (<0.5 s)
setting range cosj
0 .. 0.97 (relative scale)
response time
1 .. 100 s
operating temperature range
0 °C ... +55 °C
storage temperature range
-25 °C ... +70 °C
Output
output contact
1 changeover contact
contact material
AgNi
switching voltage (max.)
250 V AC
making/breaking capacity
1000 VA
continuous current
4 A
contact fuse
4 A
permissible switching frequency
1200 switching cycles/h
isolation per VDE 0110
rated voltage
250 V AC/DC
overvoltage category
III
pollution degree
2
test voltage (coil/contact)
2000 V, 50 Hz 1 min.
EMC test
emission per EN 50 081 T1
interference immunity
per EN 50 082 T2
Housing
type of protection (EN 60529)
housing IP50,
terminal blocks IP20
wire cross section
2.5 mm²
mounting position
any
colour
green
weight
170 g
housing dimensions WxHxL
22.5 x 75 x 100 mm
modular without
spacing
BTR NETCOM GmbH
Im Tal 2
78176 Blumberg - Deutschland
Phone +49 7702 533-0
Fax
+49 7702 533-433
www.btr-netcom.com
122006/1/02/PDF/899 100-01
Declaration of Conformity
The device meets the requirements of the CE guidelines.
Conformity was proved. The declaration of conformity is available
at the manufacturer BTR NETCOM GmbH.
Notes Regarding Device Description
These instructions include indications for use and mounting of the
device. In case of questions that cannot be answered with these
instructions please consult supplier or manufacturer.
The indicated installation directions or rules are applicable to the
Federal Republic of Germany. If the device is used in other countries
it applies to the equipment installer or the user to meet the
national directions.
Safety Instructions
Keep the applicable directions for industrial safety and the
prevention of accidents as well as the VDE rules.
Technicians and/or installers are informed that they have to
electrically discharge themselves as prescribed before installation or
maintenance of the devices.
Only qualified personnel shall do mounting and installation work
with the devices, see section “qualified personnel”.
The information of these instructions have to be read and under-
stood by every person using this device.
Symbols
Warning of dangerous electrical voltage
Danger
means that non-observance may cause risk of life,
grievous bodily harm or heavy material damage.
Qualified Personnel
Qualified personnel in the sense of these instructions are persons
who are well versed in the use and installation of such devices and
whose professional qualification meets the requirements of their
work.
This includes for example:
G
Qualification to connect the device according to the VDE specifi-
cations and the local regulations and a qualification to put this
device into operation, to power it down or to activate it by
respecting the internal directions.
G
Knowledge of safety rules.
G
Knowledge about application and use of the device within the
equipment system etc.
CPW-E12
Motor Monitoring Relay
1102810520
230 V AC - 1 ... 10 A
110281052013
230 V AC - 0.2 ... 2.5 A
Wiring Diagram
Function Diagram
Connection Examples
Connection Combined with a Frequency
Converter and a Delta-wye Circuit
Connection to Star-delta Motors