Functional Description

The cos

ϕ

monitor is used to detect an

underload. Adjustable response value
and response time. It can also be used
together with a frequency converter 
(frequency 2 to 200 Hz). Monitoring is
accomplished by recognising the phase
shift between current and voltage. This
phase angle varies according to the load
of the motor. The instrument is 
equipped with a green LED for operating
voltage indication and a red LED for
error indication.

Technical Data

Input
nominal voltage

230 V AC

power consumption (max)

1.5 VA

operating voltage range

0.9 - 1.1 x U

N

frequency range

2 ... 200 Hz

duty cycle

100 %

input voltage (motor)

230 V AC / 400 V AC

input current 

min. 0.2 A, max. 10 A

(load current)
load inrush current

100 A  (<0.5 s)

setting range cosj

0 .. 0.97 (relative scale)

response time

1 .. 100 s

operating temperature range

0 °C ... +55 °C

storage temperature range

-25 °C ... +70 °C

Output
output contact

1 changeover contact

contact material

AgNi

switching voltage (max.)

250 V AC

making/breaking capacity

1000 VA

continuous current

4 A

contact fuse

4 A

permissible switching frequency

1200 switching cycles/h

isolation per VDE 0110

rated voltage

250 V AC/DC

overvoltage category

III

pollution degree

2

test voltage (coil/contact) 

2000 V, 50 Hz 1 min.

EMC test

emission per EN 50 081 T1
interference immunity 
per EN 50 082 T2

Housing

type of protection (EN 60529)

housing IP50, 
terminal blocks IP20

wire cross section

2.5 mm²

mounting position

any

colour

green

weight

170 g

housing dimensions WxHxL

22.5 x 75 x 100 mm

modular without 

spacing

BTR NETCOM GmbH
Im Tal 2
78176 Blumberg - Deutschland

Phone  +49 7702 533-0
Fax  

+49 7702 533-433

www.btr-netcom.com

122006/1/02/PDF/899 100-01

Declaration of Conformity

The device meets the requirements of the CE guidelines.
Conformity was proved. The declaration of conformity is available
at the manufacturer BTR NETCOM GmbH.

Notes Regarding Device Description

These instructions include indications for use and mounting of the
device. In case of questions that cannot be answered with these
instructions please consult supplier or manufacturer. 
The indicated installation directions or rules are applicable to the
Federal Republic of Germany. If the device is used in other countries
it applies to the equipment installer or the user to meet the 
national directions. 

Safety Instructions

Keep the applicable directions for industrial safety and the 
prevention of accidents as well as the VDE rules. 
Technicians and/or installers are informed that they have to 
electrically discharge themselves as prescribed before installation or
maintenance of the devices.
Only qualified personnel shall do mounting and installation work
with the devices, see section “qualified personnel”. 
The information of these instructions have to be read and under-
stood by every person using this device. 

Symbols

Warning of dangerous electrical voltage 

Danger

means that non-observance may cause risk of life, 
grievous bodily harm or heavy material damage. 

Qualified Personnel

Qualified personnel in the sense of these instructions are persons
who are well versed in the use and installation of such devices and
whose professional qualification meets the requirements of  their
work. 
This includes for example:

G

Qualification to connect the device according to the VDE specifi-
cations and the local regulations and a qualification to put this
device into operation, to power it down or to activate it by
respecting the internal directions.

G

Knowledge of safety rules.

G

Knowledge about application and use of the device within the
equipment system etc. 

CPW-E12

Motor Monitoring Relay

1102810520

230 V AC - 1 ... 10 A

110281052013

230 V AC - 0.2 ... 2.5 A

Wiring Diagram

Function Diagram

Connection Examples

Connection Combined with a Frequency 
Converter and a Delta-wye Circuit

Connection to Star-delta Motors

Отзывы: