83
SV200 DC Hardware Manual
920-0126A
4/14/2017
7.2.4 Pulse Inhibit
The Pulse Inhibit function uses external input X10 in digital pulse position mode. When external input X10 is triggered, it will force the
drive to stop receiving pulse input from any source, and stop the servo motor immediately.
In factory default mode, this function is disabled. It can be set via SVX Servo Suite or P-65 (MI) directly from the drive.
Signal Name
PIN
P-65 (MI)
Condition
Function
X10
X10 (27)
2□□□
Closed
Allow input pulse
Open
Disallow input pulse
1□□□
Closed
Disallow input pulse
Open
Allow input pulse
3□□□
(default)
General purpose input, function disabled
Software Configuration
On the Drive Configuration page - Input & Output select X10 input to set up.