SV200 DC Hardware Manual
920-0126A
4/14/2017
7 Operation Mode Selection
7.1 General Function Settings
7.1.1 Drive Servo On Settings
To control servo motor enable/disable switch
1) Servo ON signal
By default, the Servo ON input (X3) is configured as follows:
Signal Name
PIN (CN2)
Condition
Function
X3
29 (X3+)
31 (X3-)
Closed
Servo motor enable Servo ON
Open
Servo motor disable Servo OFF
2) Definition for Servo On signal
Parameters P-62 (SI) and P-14 (PM) can be changed
A. When P-14 (PM) = 2, parameter settings are as follows:
P-14 (PM)
P-62 (SI)
Condition
Function
P-14 (PM) = 2
(default)
1
Closed
If P-14 (PM)=2 and P-62 (SI)=2, driver will enable at
power-up, and then switch to disable
Open
Servo Enable
2
(default)
Closed
Servo motor enable Servo ON
Open
Servo motor disable Servo OFF
3
Enable servo motor when powered ON
B. When P-14 (PM) = 5, the parameter settings are as follows:
P-14 (PM)
P-62 (SI)
Condition
Function
P-14 (PM) = 5
1
Closed
Servo motor disable Servo OFF
Open
Servo motor enable Servo ON
2
(default)
Closed
Servo motor enable Servo ON
Open
Servo motor disable Servo OFF
3
Servo motor disable when power ON
NOTE: If P-14 (PM)=5, regardless of P-62 (SI) settings, the drive will be disabled (Servo OFF) at power up. Use input X3 to enable
based on P-62 (SI) setting.
The default Power-up Mode (PM) setting (P-14) is set to a value of 5, which will cause the servo drive to power up disabled for safety
during setup and configuration. This setting may be changed in the SVX Servo Suite software with the X3 digital input configuration.
It may also be changed using the front panel on the servo drive with parameter P-14 or by using the PM command directly (see Host
Command Reference manual for details on the PM command.)
Software Configuration
On the Drive Configuration page - Input & Output, select X3 function to set up.