137
SV200 DC Hardware Manual
920-0126A
4/14/2017
P-82 (ZR)
Regen resistor value
Data Range
Default
Unit
LED Display
0 - 1000
200
Ω
200
The regeneration resistor value. SV200 DC drives dynamically calculate the continuous wattage induced into an external regeneration
resistor and must know the value of the regen resistor to do this effectively.
P-83 (ZC)
Regen resistor continuous wattage
Data Range
Default
Unit
LED Display
0 - 32000
40
W
40
The regeneration resistor wattage. SV200 DC drives calculate the continuous wattage induced into an external regeneration resistor and
must know the continuous wattage rating of the regen resistor to do this effectively.
P-84 (ZT)
Regen resistor peak time
Data Range
Default
Unit
LED Display
0 - 8000
1250
ms
5000
The regeneration resistor time constant. Calculates the peak time that the resistor can tolerate full regeneration voltage. The time is
scaled as period count. One period is 250us.
NOTE: if you need to view or set this value on the drive’s control panel refer to the following calculation:
LED
display
value
=
V x 4
Where
V
regeneration time, units (ms)
P-85 (VR)
Ripple range setting for velocity
reach
Data Range
Default
Unit
LED Display
0 - 136
0.000
rps
0
The velocity ripple value around the targeted velocity. If the difference between the actual velocity and targeted velocity is within the
ripple value, the drive will define the actual velocity as having met the target velocity value
NOTE: if you need to view or set this value on the drive’s control panel refer to the following calculation:
LED
display
value
=
V x 240
Where
V
is target veloicty, unit rps (rev/s), minimum value 1/240.
Refer to Section 7.3.3.7 Target Velocity Reached.
P-86 (TO)
Tach out counts
Data Range
Default
Unit
LED Display
0
---
0
The count value of tach out per revolution.
0: 1 * pole pairs
1: 2 * pole pairs
2: 4 * pole pairs
3: 8 * pole pairs
4: 16 * pole pairs
5: 32 * pole pairs
6: 64 * pole pairs
7: 128 * pole pairs