Troubleshooting
38. CG OM Models: No Heat With Cycle Selected, Unit Running and Calling
For Heat (continued)
120 Volt/60 Hertz/1 Phase and 208-240 Volt/60 Hertz/1 Phase Nonreversing
208-240 Volt/60 Hertz/3 Phase and 460-480 Volt/60 Hertz/3 Phase Reversing and Nonreversing
TMB2165S-b
Is there
voltage to the
input of the
cabinet
limit?
Correct wiring
between cabinet
limit and CR1.
No
Unit
operational.
Continued from
previous page
Is there
voltage to the
output of the
cabinet
limit?
Replace
cabinet limit.
Is there
voltage to
COM terminal
of the airflow
switch?
Correct wiring
between airflow
switch and cabinet
limit.
Is there
voltage to the
N.O. terminal
of the airflow
switch?
Check for proper
operation and airflow.
Replace airflow
switch if necessary.
Yes
No
Yes
No
Yes
No
Is there
voltage to the
input of the
stove limit?
Correct wiring
between stove
limit and airflow
switch.
Check for proper
airflow. Replace
stove limit if
necessary.
Is there
voltage to the
output of the
stove limit?
Correct wiring
between ignition
control and
stove limit.
Is there
voltage to
terminal 2 of
the ignition
control?
Does the
igniter
spark?
Check for proper gap on
igniter and check for
proper resistance of
ignition cable. Replace
if necessary.
Is there
voltage at
terminal 1 of
the ignition
control?
Replace
ignition control.
Is there
voltage across
the gas
valve?
Correct wiring
to gas valve.
Is there
a flame?
Check for gas flow and proper
gas pressure. Replace gas
valve or coils of gas valve.
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes