ß
IEC11000300-2-en.vsd
1
1 2
1 2
2
Ucomp
UL L
IL L Z Fwd
2
1 2
1 2
2
Ucomp
UL L
IL L Z REV
1 2
IL L
R
1 2
2
IL L Z REV
1 2
IL L
jX
1 2
2
IL L Z Fwd
IEC11000300 V2 EN
Figure 153:
Simplified offset mho characteristics for L1-to-L2 fault in zone 2
Operation occurs if 90° ≤ β ≤ 270°.
Impedance defined in the Figure
.
2
2
Z Fwd
Z Fwd
ImpedanceAng
=
Ð
2
2
Z R
Z Rev ImpedanceAng
ev
=
Ð
GUID-007D6357-B7CF-4C21-B772-2245F06C83A2 V2 EN
(Equation 56)
Voltage and current phasors selected for different measuring loops:
Phase Phase:
Sl.No
Measuring Loop
Voltage Phasor
Current Phasor
1
L1-L2
1 2
UL L
1 2
IL L
2
L2-L3
2 3
UL L
2 3
IL L
3
L3-L1
3 1
UL L
3 1
IL L
Enhanced Reach:
1MRK502052-UEN B
Section 7
Impedance protection
329
Technical manual
Содержание Relion REG670
Страница 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Страница 2: ......
Страница 44: ...38 ...
Страница 58: ...52 ...
Страница 80: ...74 ...
Страница 106: ...100 ...
Страница 482: ...476 ...
Страница 548: ...542 ...
Страница 570: ...564 ...
Страница 600: ...594 ...
Страница 608: ...602 ...
Страница 630: ...624 ...
Страница 862: ...856 ...
Страница 1094: ...1088 ...
Страница 1226: ...1220 ...
Страница 1250: ...1244 ...
Страница 1297: ...1291 ...